38 | SAMLEX AMERICA INC.
temperature rating of its insulation. The insulating material of the cables will also be
affected by the elevated operating temperature of the terminals to which these are
connected. Ampacity of cables is based on UL-1741 and the National Electrical Code (NEC)-
2014. Please see details given under “Notes for Table 3.1”.
The DC input circuit is required to handle very large DC currents and hence, the size
of the cables and connectors should be selected to ensure minimum voltage drop
between the battery and the inverter. Thinner cables and loose connections will result
in poor inverter performance and will produce abnormal heating leading to risk of
insulation melt down and fire. Normally, the thickness of the cable should be such
that the voltage drop due to the current & the resistance of the length of the cable
should be less than 2%. Use oil resistant, multi-stranded copper wire cables rated at
90º C minimum. Do not use aluminum cable as it has higher resistance per unit length.
Cables can be bought at a marine / welding supply store.
Effects of low voltage on common electrical loads are given below:
•
Lighting circuits - incandescent and Quartz Halogen:
A 5% voltage drop causes
an approximate 10% loss in light output. This is because the bulb not only receives less
power, but the cooler filament drops from white-hot towards red-hot, emitting much
less visible light.
•
Lighting circuits - fluorescent:
Voltage drop causes a nearly proportional drop in
light output.
•
AC induction motors -
These are commonly found in power tools, appliances, well
pumps etc. They exhibit very high surge demands when starting. Significant voltage
drop in these circuits may cause failure to start and possible motor damage.
•
PV battery charging circuits
- These are critical because voltage drop can cause a
disproportionate loss of charge current to charge a battery. A voltage drop greater
than 5% can reduce charge current to the battery by a much greater percentage.
MISE EN GARDE!
La section d’entrée de l’onduleur a des condensateurs de grande valeur qui sont connecté aux bornes
d’entrées. Tant que le boucle de connexion d’entrée CC (la borne (+) de la batterie
→
le fusible la
borne
→
d’entrée positive du EVO
TM
→
la borne d’entrée négative du EVO
TM
→
la borne (-) de la
batterie est complèt, les condesateurs commençeront à recharger. L’appareil prendra un courant fort
brièvement pour s’alimenter qui va produire une étincelle sur le dernier contact du boucle d’entrée
même si l’interrupteur ON/OFF du l’onduleur est dans la position OFF.
Assurez que le fusible est insèrer seulement après que toutes les connexions sont faites dans le
boucle pour que des étincelles se produisent seulement à l’endroit du fusible.
Le flux du courant dans un conducteur est opposé par la résistance du conducteur. La résistance du conducteur
est corrélative à la longueur du conducteur et inversement corrélatif à son diamètre (l’épaisseur). La résistance
dans un conducteur produit des effects indésirables comme une perte de tension et une surchaffe. La taille
(l’épaisseur) des conducteurs est classée par le AWG (American Wire Guage). Les conducteurs qui sont plus épais
que la taille AWG #4/0 sont classé par MCM/kcmil.
SECTION 3 |
Installation