94 | SAMLEX AMERICA INC.
If the unit was in Inverting Mode [Blue LED “ON” (12, Fig 2.1) steady] and the Mode
is set to Equalization as above by pressing the ON/OFF Push Button for 1 second, the
unit will undergo Equalization Mode whenever qualified AC input is available from
Grid / Generator and the unit enters Charging Mode. To terminate Equalization Mode
prematurely before its completion, press the ON/OFF Push Button for 1 second.
NOTE:
Procedure described above is to be used when the optional Remote
Control EVO-RC-PLUS has NOT been plugged into the RJ-45 Remote
Control Jack (7, Fig 2.1).
Please note if the Remote Control has
been plugged into the RJ-45 Jack, the above procedure cannot be
activated and the ON/OFF of Equalization Mode will be controlled
by the Remote Control EVO-RC-PLUS.
Using Optional Remote Control EVO-RC-PLUS:
Please refer to the following
Sections of the Owner's Manual for EVO-RC-PLUS:
- Section 4.1.3.1, Fig 4.2, Screen No. 12 "EQUALIZE-4STAGES"
- Section 4.4.2.12 , set up procedure for parameter "EQUALIZE-4STAGES" setting at "1=Yes"
5.11 TWO-STAGE CHARGING PROFILES
In 2-Stage Profile, the battery is charged in Bulk Stage first and then in Absorption Stage.
There is no 3
rd
Stage. Please refer to Fig 5.1 for typical Voltage and Current Curves. Consider
the curves for the Bulk and Absorption stages only.
NOTE:
The 2
nd
Stage, i.e. "Absorption Stage" may also be referred to as "Float Stage"
in some applications like in Lithium Battery charging, and charging Lead Acid
batteries with load (battery backup applications) where the voltage setting of the 2
nd
Absorption stage is lowered to the level corresponding to Float Stage level.
There are 2 options for Charging Profiles for 2-Stage Charging – (i) Type 1 and (ii) Type 2.
Please refer to Table 5.2 for details.
2-Stage Charging Profiles are typically used for charging Lead Acid Batteries with load
(battery backup application) and for charging Lithium Batteries. Please refer to Section 5.12
below for details on charging Lithium Batteries
5.12 CHARGING LITHIUM BATTERIES
!
CAUTION!
The Battery Management System (BMS) that comes with the Lithium Battery being
used may need to have control over charging and discharging of the battery. For
this, Pins 4 and 5 of the Temperature Sensor Jack (6, Fig 2.1) may be used to feed
potential free contact closing signal from the BMS to “Stop Charging” or “Stop
Inverting. See details given below.
!
ATTENTION!
Le système de gestion de la batterie (BMS) qui vient avec la batterie au lithium utilisé peut avoir besoin
d'avoir le contrôle de charge et décharge de la batterie. Pour cela, les broches 4 et 5 du capteur de
température (6, figure 2.1) peut être utilisé pour l'alimentation contact libre de signal de fermeture de la
RBE en "Stop" ou "arrêt de charge de l'inversion. Voir les détails donnés ci-dessous.
SECTION 5 |
Battery Charging in Evolution
TM
Series
Summary of Contents for Evolution EVO-1212F
Page 109: ...SAMLEX AMERICA INC 109 Notes...
Page 110: ...110 SAMLEX AMERICA INC Notes...
Page 111: ...SAMLEX AMERICA INC 111 Notes...