3.14.2.2 EVO-1212F-HW and EVO-1224F-HW: AC Side Grounding of Typical
Shore Based Installation
Refer to the Installation Diagram for Typical Shore Based Installation for EVO-1212F-HW and
EVO-1224F-HW at Fig 3.13
(a)
AC Input Grounding:
The metal chassis of EVO
TM
gets bonded to the Grounding Electrode
(GE) / “Ground Rod” of the premises as follows:
• The metal chassis of EVO
TM
is connected to the “INPUT GND” Terminal (23) of the AC
Input / Output Terminal Block (20) in EVO
TM
• The “INPUT GND” Terminal (23) of the AC Input / Output Terminal Block (20) in EVO
TM
gets connected to the Grounding Bus Bar (G-B) in the Grid Electrical Panel through the
grounding wire of AC input connection
• The Grounding Bus Bar (G-B) in the Grid Electrical Panel is bonded to Earth Ground
through the Grounding Electrode (GE) / “Ground Rod” of the premises
(b)
AC Output Grounding:
The metal chassis of the AC load(s) gets connected to the
Grounding Electrode (GE) / “Ground Rod” of the premises as follows:
• The metal chassis of the AC load(s) is connected to the Grounding Bus Bar (G-B) of the
Electrical Sub Panel for EVO
TM
Output
• Grounding Bus Bar (G-B) of the Electrical Sub Panel for EVO
TM
Output is connected to
metal chassis of EVO
TM
through the “OUTPUT GND” Terminal (26) of the AC Input /
Output Terminal Block (20) in EVO
TM
.
• The metal chassis of EVO
TM
is connected to the “INPUT GND” Terminal (23) of the AC
Input / Output Terminal Block (20) in EVO
TM
• The “INPUT GND” Terminal (23) of the AC Input / Output Terminal Block (20) in EVO
TM
gets connected to the Grounding Bus Bar (G-B) in the Grid Electrical Panel through the
grounding wire of AC input connection
• The Grounding Bus Bar (G-B) in the Grid Electrical Panel is bonded to Earth Ground
through the Grounding Electrode (GE) / “Ground Rod” of the premises
3.14.3 AC Side Grounding of Typical RV / Mobile Installation
3.14.3.1 EVO-1212F and EVO-1224F: AC Side Grounding of Typical
RV / Mobile Installation
Refer to the Installation Diagram for Typical RV / Mobile Installation for EVO-1212F and EVO-
1224F at Fig 3.14.
(a)
AC Input Grounding:
The metal chassis of EVO
TM
gets bonded to (i) the RV / Vehicle
Chassis Ground when not connected to Grid Power and (ii) to the Grounding Electrode
(GE) / Ground Rod of the Grid Power System of the premises when connected to Grid
Power through the Grid Power Supply Cord as follows:
• The metal chassis of EVO
TM
is connected to the Grounding Pin (G) of the AC Power Inlet
Plug (9)
• The Grounding Pin (G) of the AC Power Inlet Plug (9) gets connected to the Grounding
Bus Bar (G-B) in the Electrical Panel of the RV / vehicle through the grounding wire of
AC input connection.