TABLE 6.5 PROGRAMMABLE AND DEFAULT PARAMETERS - GROUP "INPUT HIGH LIMIT"
Group
Parameter name
Setting range
Default value
EVO-1212F
EVO-1212F-HW
EVO-1224F
EVO-1224F-HW
EVO-1212F
EVO-1212F-HW
EVO-1224F
EVO-1224F-HW
INPUT -
HIGH LIMIT
RESET VOLTAGE
120.0 – 150.0V
125.0V
CUT OFF VOLT 1
120.0 – 150.0V
135.0V
DETECT TIME 1
0 – 2000 cycle
60 cycle
CUT OFF VOLT 2
120.0 – 150.0V
140.0V
DETECT TIME 2
0 – 2000 cycle
15 cycle
CUT OFF VOLT 3
120.0 – 150.0V
145.0V
DETECT TIME 3
0 – 2000 cycle
1 cycle
TABLE 6.6 PROGRAMMABLE AND DEFAULT PARAMETERS - GROUP "OTHER FUNCTIONS"
Parameter name
Setting range
Default Value
EVO-1212F
EVO-1212F-HW
EVO-1224F
EVO-1224F-HW
EVO-1212F
EVO-1212F-HW
EVO-1224F
EVO-1224F-HW
“POWER SAVING”
0 = Disable , 1 = Enable
0 = Disable
“ENTER POINT”
4 – 50W
6W
“WAKE UP POINT”
5 – 50W
7W
“REMOTE SWITCH”
For ON /OFF control
through external 12V
signal fed to Remote
ON / OFF terminals on
the Front Panel (15,
Fig 2.1)
0 = Button Type
: 12V signal is fed
through Push Button Type of Switch
Pressing of Push Button > 2 sec
will switch the unit ON
When ON, pressing Push Button
> 5 sec will turn the unit OFF
1 = Switch Type:
12V signal is fed
through contacts of Toggle Type of
Switch or relay contact
ON condition (contacts closed)
will turn the unit ON
OFF condition (contacts open)
for 2 sec will switch the unit OFF
0
= Button Type
CAUTION!
ON/OFF Logic also controls the
operation of the ON/OFF Button on the
front panel (11, Fig 2.1). The Default setting
is "Button Type".
If the ON/OFF Control is changed to external
"Remote Switch", it will not be possible to
switch ON/OFF the EVO
TM
Inverter/Charger
from the front panel ON/OFF Push Button
because it will work with Switch Type
Logic. It will be ON only as long as the Push
Buttom is kept pressed and will switch OFF
when released.
“COMM ID”
(Communication ID for
optional Remote Control
EVO-RC-PLUS)
1 - 255
1
“BUZZER”
0 = OFF ; 1 = ON
1 = On
“DISCHARGE BEEP”
(Beeping in “Discharg-
ing / Inverter Mode”)
0 = OFF ; 1 = ON
0 = Off
“DEFAULT RESET”
0 = No ; 1 = YES
0 = No
DATA LOG TIME
(For Optional Remote
Control EVO-RC-PLUS)
0 = Disable 3 = 30 sec 6 = 10 min
1 = 1 sec 4 = 60 sec
1
2 = 10 sec 5 = 5 min
1
1 = 1 sec
PARAMETER SAVE
(For Optional Remote
Control EVO-RC-PLUS)
0 = No
1 = Yes
0 = No
TEMP UNIT
0 = C ; 1 = F
0 = C
PASSWORD DISABLE
0 = No ; 1 = Yes
0 = No
SECTION 6 |
Operation, Protections and Troubleshooting