66
SALICRU
9. ANNEX I. TECHNICAL SPECIFICATIONS
9.1. INTERNATIONAL STANDARDS
Information
Standards
Quality and Environmental Management
ISO 9001 & ISO 14001
Uninterruptible power systems (UPS). Safety
requirements
IEC/EN 62040-1
Safety requirements for power electronic converter
systems and equipment. Part 1: General
IEC/EN 62477-1
Uninterruptible power systems (UPS). Electromagnetic
compatibility (EMC) requirements
EN-IEC 62040-2
Uninterruptible power systems (UPS). Method of
specifying the performance and test requirements
VFI-SS-11 (EN-IEC 62040-3)
Tab. 13.
Standards applied.
9.2. ENVIRONMENTAL CHARACTERISTICS
Information
Environmental
Pollution degree
PD2
UV resistance
Yes, by epoxy-polyester paint
Mechanical conditions: vibration, shock, fall...
Class 3M1 (IEC 60721-3-3)
Overvoltage category
OVC II
Protection
Class I
IP protection degree
IP20
Acoustic noise at 1 metre distance
< 54.0 dB (A)
Operating altitude
2400 m a.s.l.
(1)
Relative humidity
0.. 95%, no condensation
Operating temperature
0.. 40 ºC
(2)
(battery life is reduced by 50% for every 10ºC increase over 20ºC)
Storage and transport temperature
–15.. +60 (UPS) / 0.. +35 (Battery)
(1)
Above 2400m. and up to 5000 m. there is a power derating of 1% per 100 m.
(2)
Up to 55ºC with power derating.
Fig. 70.
Environmental characteristics
9.3. MECHANICAL CHARACTERISTICS
Cabinet specifications
30 kVA
40 kVA
50 kVA
60 kVA
80 kVA
Dimensions (Depth × Width × Height)
909 x 377 x 1042 mm
919 x 560 x 1654 mm
Weight
without batteries
70 kg
150 kg
with batteries (standard aut.)
290 kg
480 kg
Colour
RAL 9005
Degree of protection, IEC (60529)
IP20
Tab. 14.
Mechanical characteristics