28
SALICRU
SALICRU
3.
Turn the manual bypass switch
8
from «BYPASS» to «UPS».
The load will be supplied through the AC grid through the in-
ternal UPS or stabiliser static bypass.
Any transfer manoeuvring will be done with the
UPS or stabilizer on «Bypass mode».
4.
Put the protection cover
13
of the manual bypass switch back,
otherwise the UPS inverter or stabiliser will not start up.
5.
Turn the UPS inverter or stabiliser «On», by respecting the
steps stated in their documentation (user's manual).