25
6. INSTALLATION.
•
Read and respect the Safety instructions, described in
section 2 of this document. The fact of omitting any of
the stated indications can cause serious or very serious acci-
dents to the surrounding, as well as failures in the equipment
and/or loads connected to it.
6.1. RECEPTION OF THE EQUIPMENT.
6.1.1. Reception, unpacking and contents.
•
Reception. Check that:
Data of the label sticked on the packaging corresponds
to the ones stated in the order. And once it is unpacked,
check the previous data with the ones in the nameplate of
the own manual bypass unit.
In case of any discrepancies, make the nonconformity,
quoting the references in the delivery note.
It has not been damaged during transport.
•
Contents.
Rack mounting equipment.
1 Schuko/C19 power supply cable + 2 C20/C19 power
supply cables for AC input (3 kVA model).
Bypass signal cable to be connected with TWIN PRO2/
PRO3 or RT2 /RT3UPSs (6 and 10 kVA models).
Angles supports for 19" rack mounting and their screws.
User's manual in hardcopy and warranty.
•
Once the reception is finished, if it is not going to be installed in
the next days, it is recommended to keep the equipment back
in its original packaging as a preventive measure.
•
As regards to the packaging, when it is going to be disposed,
do it in accordance with the regulations in force.
It is advised to keep it for year, at least.
6.2. LOCATION AND CONSIDERATIONS.
•
Remove the angles and screws from the plastic bag and as-
semble them on the rack mounting bypass.
•
These devices are designed to be integrated into rack cabinets.
Illustrations from Fig 5 and 6 are mere examples and the first
one shows the wall mounting version for 16 A model.
UPS or stabilizer
19" rack installation.
Wall mounting installation.
Fig. 5. Example of 3 kVA manual bypass installation.
UPS or stabilizer
Fig. 6. Example of 6 and 10 kVA manual bypass installation.
6.3. WIRING.
•
Any equipment connection, control included (interface,
remote control, ...), will be done with all the switched
OFF and with no mains present (power supply switch of the
UPS to «Off»).
•
Do not forget that the UPS is an electrical generator, so
the end-user must take the needed cautions against
the direct and indirect contacts, in case the installation has
one.
•
For 6 and 10 kVA manual bypass connected to a UPS, the docu-
mentation of itself will be taken into account, as regard the
«Backfeed protection». Also, in the installation itself, it is also
stated the cross cable section and protection size and features,
etc.. for a determined power rate. At least proceed according
to these recommendations.
•
For 6 and 10 kVA models, remove the terminal protection cover
11
. Once the connection actions are finished, put it back.
Cover
11
has two cable glands
12
for the use of the
cable entrance. Before connecting the cables to their
respective terminals, remember to pass them through
BM-R
Rack mounting manual bypass
USER'S MANUAL
Summary of Contents for BM-R
Page 1: ...MANUAL DE USUARIO BYPASS MANUAL EN RACK BM R 3 6 y 10 kVA ES EN FR PT DE...
Page 2: ...2 SALICRU SALICRU...
Page 15: ...15 BM R Bypass manual en rack MANUAL DE USUARIO ES...
Page 17: ...USER S MANUAL BYPASS MANUAL EN RACK BM R3 6and10kVA EN...
Page 18: ...18 SALICRU SALICRU...
Page 31: ...31 BM R Rack mounting manual bypass USER S MANUAL EN...
Page 33: ...FR MANUEL D UTILISATEUR BYPASS MANUEL SUR RACK BM R3 6et10kVA...
Page 34: ...34 SALICRU...
Page 47: ...47 FR BM R Bypass manuel sur rack MANUEL D UTILISATEUR...
Page 49: ...PT MANUAL DO UTILIZADOR BYPASS MANUAL EM RACK BM R 3 6 e 10 kVA...
Page 50: ...50 SALICRU SALICRU...
Page 63: ...63 PT BM R Bypass manual em rack MANUAL DO UTILIZADOR...
Page 65: ...BETRIEBSANLEITUNG MANUELLER BYPASS IN RACKAUSF HRUNG BM R3 6und10kVA DE...
Page 66: ...66 SALICRU...
Page 79: ...79 BM R Manueller Bypass in Rackausf hrung BETRIEBSANLEITUNG DE...