8
| EN
AMBERAIR COMPACT CX V v2019.04
FILTER DATA
Filter code
Type
Width, [mm] Height, [mm] Depht, [mm] Bag nr.
Class*
Efficiency*
* - according to ISO 16890.
3.4. OPERATING CONDITIONS
Place of operation
Indoors / outdoors / indoors and outdoors /
outdoors with special accessories
Operation in explosive environment
prohibited
Transporting of the polluted air
prohibited
Outdoor air temeperature without preheater (
Salda Antifrost**
off)
-5/+40*
°C
Outdoor air temeperature without preheater (
Salda Antifrost**
on)
-15/+40
°C
Outdoor air temperature with 100% by-pass***
-23/40
°C
Outdoor air temperature with segmental by-pass***
-30/40
°C
Outdoor air temperature limits with a selected pre-heater on an air duct
-40/+40
°C
Outdoor air max humidity
90
%
Temperature limits of an extracted air
+15 / +40
°C
Extract air max humidity
60
%
Maximum room temperature for installing the unit
0 / +40
°C
The air handling units installed outdoors shall be started only when the following obligatory conditions established by the manufacturer are met:
• Units that are stored at the site before installation shall be sealed using additional means in order to prevent the accumulation of moisture inside
the unit.
• If the unit is installed and is not started for continuous operation, it must be ensured that no warm/humid air enters the unit through air ducts and
that no moisture condensates inside the unit.
• If the ventilation units stand idle for a long time or are started infrequently, the system must be blown down at the maximum capacity 1/24 h to
dehumidify.
• Voltage to the automatics of the unit is installed and connected; the system of water products is filled with glycol/water.
In case of failure to comply with the requirements set out above, the manufacturer shall have the right not to apply the warranty in respect of the
occurrence of moisture/water in damaged components.