AMBERAIR COMPACT CX V v2019.04
5.5.3. PLACE REQUIREMENTS FOR THE EQUIPMENT AND MOUNTING POSITIONS
1. The installation position only in the horizontal direction.
2. Install the supporting legs.
3. AmberAir Compact are assembled from separate sections.
4.
They must be adjusted without a gradient.
5.
Leave space in the front (1,5xL) that it would be sufficient to open the doors and to remove or install a required component.
Space for door opening
L, [mm]
2000
5.6. DARINAGE
• After installing the air handling unit, the condensate drainage system should be connected: connect the siphon (2) (shown at the bottom of the
picture) to the condensate trap (1) of the heat recovery unit.
• Two siphons are used at each AmberAir Compact CX V product because two condensate drip trays are installed at each of those units).
• The siphon (2) is connected with the sewage system via a pipe (3), which can be made either of metal, plastic or rubber. It should have a gradient
of at least 3° (a metre of the pipe should descent by 55 mm)!
• Prior to starting the recovery unit, the system should be filled with 0.5 litre or more water (the siphon (2) should always be filled up) and make
sure that water goes to the sewage system (4))! Otherwise, the room may be flooded when operating the recovery unit!
• The condensate drainage system should be operated in a room with an ambient temperature not below 0 °C! If it may drop below 0 °C, the
system must be protected with thermal insulation with additional installation of a heating cable and thermostat.
• The siphon (2) should not necessarily be downstream the recovery unit but below it.
• The legs of AmberAir Compact products of sizes 1-5 CX V are fitted with condensate pipe protection to prevent it from damage when lifted by a
forklift. When connecting the condensate drainage system, this protection should be removed (it is a component intended for transportation only).