7.6.2. AIR DAMPER MAINTENANCE AMBERTAIR COMPACT 6-7 CX V
Removal of the damper
•
Disconnect the damper wires from the automatics. Unscrew the screws holding the sealing blocks (there are 2 sealing blocks, from both sides
of the partition). Remove the wires together with the sealing blocks.
•
Remove the filter above the damper (see Filters Maintenance).
•
Unscrewed the screw holding the damper clamping part. Remove the clamping part.
•
Open the damper top and install the damper clamping part turned around and turned over (screw up the screw). Fold out the valve fixing part.
•
Take the damper with both hands and pull it. It lifts slightly and is drawn out from the product as far as the slide allows. Fold back the damper
fixing part 1. Fold down the slide fixing part 2.
•
Carefully remove the damper. Unscrew the screw and remove the fixing part (if the heat exchangers should also be removed).
Installation of the damper
•
Screw up the damper clamping part 1 (shown on the figure). Shift the slide 2 and fold down the slide fixing part 3. The damper bottom rests onto
the slide, and the damper top rests onto the damper clamping part. Carefully push out the damper.
•
Fold back the slide fixing part 2. Push in the slide and the damper against stop. When pushing the slide, protect your fingers!!! The damper to
-
gether with the slide moves down. Unscrew the screw and remove the damper clamping part. Turn around, turn over and screw up the damper
clamping part. Put the wires with the sealing blocks through the hole in the partition. Screw up the wire sealing blocks (from both sides of the
partition). Connect the wires to the automatics according to the connection diagram.