Light Commercial R410A on-off
S13-01.01.13en
10.
The Specification of Power
Indoor Units. HSP Duct Type
79
MODEL
24
36-60
Power
Phase
1-phase
3-phase
Frequency and Voltage
220-240V, 50Hz
380-415V~ 50Hz
Circuit Breaker/ Fuse (A)
30/15
40/25
Indoor Unit Power Wiring (mm
2
)
3x2.5
5x2.5
Indoor/Outdoor Connecting
Wiring (mm
2
)
Ground Wiring
-----
-----
Outdoor Unit Power Wiring
3x2.5
5x2.5
Strong Electric Signal
3-core cable 3x1.5
3-core cable 3x2.5
Weak Electric Signal
2-core shielded wire
2x0.75
-----