Light Commercial R410A on-off
S13-01.01.13en
f. Full-water malfunction
Full-water malfunction
No
Check whether the water-level switch is inserted well
Insert the water-level switch well
Yes
Yes
Check whether the water-level switch is broken
Replace the water-level switch
No
No
Replace the water pump
Check whether the water pump is normal
Yes
Check PCB board or replace the main control board
g.
Temperature sensor error of water pump
E5
No
Whether the resistance of the temp. sensor is 10K
Replace temp. sensor
Yes
Replace indoor PCB
Outdoor Units. Troubleshooting
101