![Sakata SIB-100BAY Service Manual Download Page 44](http://html.mh-extra.com/html/sakata/sib-100bay/sib-100bay_service-manual_801520044.webp)
Light Commercial R410A on-off
S13-01.01.13en
2.
Specifications
Notes:
1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 27
°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal)
2. Nominal heating capacities are based on the following conditions:
Indoor temp: 20
°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal)
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic
room.
Indoor Units. Ceiling & Floor
43
Model
SIB-50TAV
SIB-60TAV
Power supply
V-ph-Hz
220~240-1-50
220~240-1-50
Cooling
Capacity
Btu/h
18000
24000
kW
5.28
7.0
Input
W
1726
2423
EER
3.07
2.93
Heating
Capacity
Btu/h
20000
26000
kW
5.86
7.62
Input
W
1863
2415
COP
3.22
3.15
Indoor fan motor
Model
YSK55-4L
YSK55-4L
Qty
1
1
Input
W
125/105/85
125/105/85
Capacitor
uF
2.5uF/450V
2.5uF/450V
Speed(Hi/Mi/Lo)
r/min
1310/1190/1040
1310/1190/1040
Indoor coil
Number of rows
2
3
Tube pitch(a)
×row pitch(b)
mm
25.4
×22
21
×13.37
Fin spacing
mm
1.3
1.3
Fin type (code)
Hydrophilic aluminum
Hydrophilic aluminum
Tube outside dia. and type
mm
7 Inner grooved
copper tube
7 Inner grooved copper
tube
Coil length
× height× width
mm
804
×252×26.74
804
×252×40.11
Number of circuits
3
4
Indoor air flow(Hi/Mi/Lo)
m
3
/h
800/600/500
1200/900/700
Indoor noise level (sound pressure)
dB(A)
43/41/38
45/43/40
Indoor unit
Dimension (W
×H×D)
mm
990
×203×660
990
×203×660
Packing (W
×H×D)
mm
1037
×238×739
1037
×238×739
Net/Gross weight
kg
24/30
24/30
Refrigerant type
R410A
R410A
Design pressure
MPa
4.2/1.5
4.2/1.5
Refrigerant piping
Liquid side/Gas side
mm
6.4/
12.7
9.5/
15.9
Drainage water pipe diameter
mm
OD
25
OD
25
Controller
RG36C/BG(C)E
RG36C/BG(C)E
Operation temperature
℃
17-30
17-30
Summary of Contents for SIB-100BAY
Page 1: ...S13 01 01 13en Light Commercial Air Conditioner R410A ON OFF Service Manual 2013 ...
Page 6: ...Light Commercial R410A on off S13 01 01 13en 2 2 Outdoor Units General Information 5 ...
Page 48: ...Light Commercial R410A on off S13 01 01 13en 4 Service Space Indoor Units Ceiling Floor 47 ...
Page 68: ...Light Commercial R410A on off S13 01 01 13en 3 Dimensions Indoor Units HSP Duct Type 67 ...
Page 69: ...Light Commercial R410A on off S13 01 01 13en Indoor Units HSP Duct Type 68 ...
Page 91: ...Light Commercial R410A on off S13 01 01 13en 5 Wiring Diagrams SOB 50VA Outdoor Units 90 ...
Page 92: ...Light Commercial R410A on off S13 01 01 13en SOB 60VA SOB 100YA Outdoor Units 91 ...
Page 93: ...Light Commercial R410A on off S13 01 01 13en SOB 140YA SOB 200YA Outdoor Units 92 ...