Light Commercial R410A on-off
S13-01.01.13en
SIB-140DAY
Cooling
Heating
Remark:
TC : Total capacity ; kW
SC: Sensible heat capacity ; kW
Input: Input power ; kW
Indoor Units. HSP Duct Type
74
Heating
Outdoor conditions
Indoor Conditions
(DB)
(kW)
24/18
ºC
DB/WB
7/6ºC
DB/WB
2/1ºC
DB/WB
-5/-6
ºC
DB/WB
-7/-8
ºC
DB/WB
15ºC
TC
19.50
15.75
12.90
11.70
10.95
Input
5.40
4.65
4.00
3.75
3.55
20ºC
TC
18.90
15.00
12.15
11.40
10.50
Input
5.90
5.00
4.40
4.05
3.80
27ºC
TC
17.70
14.10
11.40
11.10
9.90
Input
6.25
5.40
4.75
4.40
4.10
Cooling
Outdoor conditions (DB)
Indoor Conditions
(kW)
18ºC
21ºC
28ºC
35ºC
43ºC
21/15
ºC DB/WB
TC
14.84
14.42
13.72
13.02
12.46
SC
10.83
10.67
10.56
10.42
10.47
Input
4.26
4.42
4.79
5.00
5.16
24/17
ºC DB/WB
TC
15.26
14.84
14.14
13.44
12.60
SC
11.29
11.13
11.03
10.89
10.58
Input
4.52
4.68
5.00
5.22
5.48
27/19
ºC DB/WB
TC
15.54
15.12
14.42
14.00
13.02
SC
11.34
11.19
11.10
10.92
10.68
Input
4.63
4.79
5.06
5.32
5.59
32/23
ºC DB/WB
TC
15.96
15.40
14.84
14.56
13.44
SC
13.41
13.09
12.91
12.81
12.50
Input
4.84
5.00
5.22
5.59
5.80
Summary of Contents for SIB-100BAY
Page 1: ...S13 01 01 13en Light Commercial Air Conditioner R410A ON OFF Service Manual 2013 ...
Page 6: ...Light Commercial R410A on off S13 01 01 13en 2 2 Outdoor Units General Information 5 ...
Page 48: ...Light Commercial R410A on off S13 01 01 13en 4 Service Space Indoor Units Ceiling Floor 47 ...
Page 68: ...Light Commercial R410A on off S13 01 01 13en 3 Dimensions Indoor Units HSP Duct Type 67 ...
Page 69: ...Light Commercial R410A on off S13 01 01 13en Indoor Units HSP Duct Type 68 ...
Page 91: ...Light Commercial R410A on off S13 01 01 13en 5 Wiring Diagrams SOB 50VA Outdoor Units 90 ...
Page 92: ...Light Commercial R410A on off S13 01 01 13en SOB 60VA SOB 100YA Outdoor Units 91 ...
Page 93: ...Light Commercial R410A on off S13 01 01 13en SOB 140YA SOB 200YA Outdoor Units 92 ...