Light Commercial R410A on-off
S13-01.01.13en
10. The Specification of Power
Cooling & heating
Indoor Units. Four-way Cassette Type
38
Type
24000 Btu/h
36000-48000 Btu/h
60000 Btu/h
Power
Phase
1-phase
3-phase
3-phase
Frequency and
Voltage
220-240V, 50Hz
380-415V, 50Hz
380-415V, 50Hz
Circuit Breaker/ Fuse (A)
40/25
25/15
40/25
Indoor Unit Power Wiring (mm
2
)
3
×2.5
5
×2.5
5
×2.5
Indoor/Outdoor Connecting Wiring
(mm
2
)
Ground Wiring
4.0
2.5
2.5
Outdoor Unit
Power Wiring
3
×2.5
5
×2.5
5
×2.5
Strong Electric
Signal
3
×2.5
3
×1.0
3
×2.5
Weak Electric
Signal
2-core shield wire
2
×0.75