Light Commercial R410A on-off
S13-01.01.13en
5.5 SIB-200TAY
Cooling
Heating
Remark:
TC : Total capacity ; kW
SC: Sensible heat capacity ; kW
Input: Input power ; kW
Indoor Units. Ceiling & Floor
52
Heating
Outdoor conditions
Indoor
Conditions (DB)
(kW)
24/
18ºC
DB/WB
7/
6ºC
DB/WB
2/
1ºC
DB/WB
-5/-
6ºC
DB/WB
-7/-
8ºC
DB/WB
15ºC
TC
24.70
19.95
16.34
14.82
13.87
Input
6.75
5.81
5.00
4.68
4.43
20ºC
TC
23.94
19.00
15.39
14.44
13.30
Input
7.37
6.25
5.50
5.06
4.75
27ºC
TC
22.42
17.86
14.44
14.06
12.54
Input
7.81
6.75
5.93
5.50
5.12
Cooling
Outdoor conditions (DB)
Indoor Conditions
(kW)
18ºC
21ºC
28ºC
35ºC
43ºC
21/
15ºC DB/WB
TC
16.96
16.48
15.68
14.88
14.24
SC
12.38
12.20
12.07
11.90
11.96
Input
5.25
5.45
5.91
6.17
6.37
24/
17ºC DB/WB
TC
17.44
16.96
16.16
15.36
14.40
SC
12.91
12.72
12.60
12.44
12.10
Input
5.58
5.77
6.17
6.43
6.76
27/
19ºC DB/WB
TC
17.76
17.28
16.48
16.00
14.88
SC
12.96
12.79
12.69
12.48
12.20
Input
5.71
5.91
6.23
6.56
6.89
32/
23ºC DB/WB
TC
18.24
17.60
16.96
16.64
15.36
SC
15.32
14.96
14.76
14.64
14.28
Input
5.97
6.17
6.43
6.89
7.15
Summary of Contents for SIB-100BAY
Page 1: ...S13 01 01 13en Light Commercial Air Conditioner R410A ON OFF Service Manual 2013 ...
Page 6: ...Light Commercial R410A on off S13 01 01 13en 2 2 Outdoor Units General Information 5 ...
Page 48: ...Light Commercial R410A on off S13 01 01 13en 4 Service Space Indoor Units Ceiling Floor 47 ...
Page 68: ...Light Commercial R410A on off S13 01 01 13en 3 Dimensions Indoor Units HSP Duct Type 67 ...
Page 69: ...Light Commercial R410A on off S13 01 01 13en Indoor Units HSP Duct Type 68 ...
Page 91: ...Light Commercial R410A on off S13 01 01 13en 5 Wiring Diagrams SOB 50VA Outdoor Units 90 ...
Page 92: ...Light Commercial R410A on off S13 01 01 13en SOB 60VA SOB 100YA Outdoor Units 91 ...
Page 93: ...Light Commercial R410A on off S13 01 01 13en SOB 140YA SOB 200YA Outdoor Units 92 ...