PDM20 Series
- 57 -
4. Three wire 24V sensor wiring diagram
M1 M2 GND +VO AI
2.Set pressure parameters:
P0.38=1
P0.03=10
P0.04=1
P0.05=24
3.Set target pressure:
P0.00=3.0
P0.01=0.3
4.Choose auto-start mode:
P0.14=11
5.Check rotation direction
of pump:
Shortly start pump, check
the direction of pump, if
the pump direction error,
change the pdrameter
P0.02.
6.Observe the effect of
constant pressure:
Observe the effect of
constant pressure, if the
pressure is constant, that is
OK; if the pressure
fluctuations large , please
reference common fault
handling tutorial.
8.Warm tips
a: Water supply system
must be equipped with a
check valve, five way valve
is a kind of check valve.
b: For a new pump,when it
runs without pressure,
emptying is suggested.
PDM20-Three wire 24V sensor wiring diagram
Pressure
transmitter
Type: PT1100
Power: 24VDC
Range: 0-1Mpa
Output: 4-20mA
Power line
:
red
Singal line
:
green
Ground line
:
balck
Black line connected to GND
Red line connected to +VO
Green line connected to AI
Before connecting, check the
voltage bVO and GND
using a multimeter
1.Installation and wiring:
Connect the power cable
and the sensor cable
according to the diagram.
7.Sleep test:
Close the water outlet, the
drive output frequency will
be reduced until shutdown;
if it can not sleep, please
refer to the common fault
handling tutorial.
Summary of Contents for PDM20 series
Page 1: ...PDM20 Smart Mini Pump Drive User Manual Version Code PDM20 EN 60200256 1612 ...
Page 12: ...PDM20 Series 11 Example Modify P0 02 from 0 to 1 Remarks 0 1MPa 100kPa 1bar 1kgf cm2 ...
Page 14: ...PDM20 Series 13 2 3Dimensions Unit mm 136 116 176 158 114 105 124 138 ...
Page 59: ...PDM20 Series 58 V1 1 Inverter ...