PDM20 Series
- 37 -
After selecting sleep mode 1 by parameter P0.08, the SPD will detect whether
feedback pressure is higher than set pressure. If yes, the SPD will start sleep
detection. After PID sleep detection delay set by P0.09, if feedback pressure is still
higher than set pressure, SPD will decrease output frequency gradually to sleep
detection low level hold frequency set by P0.11. After sleep detection low level
hold frequency waiting time, if feedback pressure is still higher than set pressure,
the SPD decreases output frequency to 0Hz and enter standby. If in above process,
feedback pressure is lower than set pressure, the SPD will judge as invalid sleep
detection and come back to PID adjustment status.
When sleep mode 2 is selected, the system will try to sleep according to water
consumption condition automatically.
After the SPD enters standby, if feedback pressure is lower than PID sleep
threshold, SPD will start wakeup detection. After PID wakeup detection delay set
by P0.10, if feedback pressure is still lower than wakeup pressure threshold,
wakeup is successful and SPD comes back to PID adjustment status; else, wakeup
fails. Too high PID sleep threshold may cause frequent start and stop of the SPD.
Too low PID sleep threshold may cause deficient pressure.
Notes: sleep holding frequency of different water supply system is different. When
there is no water outside and the water tap is turned off, but the pump is still
running, increase P0.11 to sleep holding frequency.
P0.14
Automatically
start self-reset at
power on
Ones
:
Auto-start choices
0
:
OFF
1
:
ON
Tens
:
Fault self-reset choices
0
:
OFF
1
:
ON
10
By default, self-reset is
ON and auto-start is
OFF.
P0.15
Auto-start delay
at power on
0.0
~
100.0
s
5.0
Delay time before
auto-start at power on
Summary of Contents for PDM20 series
Page 1: ...PDM20 Smart Mini Pump Drive User Manual Version Code PDM20 EN 60200256 1612 ...
Page 12: ...PDM20 Series 11 Example Modify P0 02 from 0 to 1 Remarks 0 1MPa 100kPa 1bar 1kgf cm2 ...
Page 14: ...PDM20 Series 13 2 3Dimensions Unit mm 136 116 176 158 114 105 124 138 ...
Page 59: ...PDM20 Series 58 V1 1 Inverter ...