5.1 Fault Codes Description
Fault
code
Fault type
Possible reasons
Solution
E001
Invert cells
fault
1
.
Too fast acceleration
1
.
Increase acceleration time
2
.
IGBT inside broken
2
.
Seek for support
3
.
Malfunction caused by
interference
3
.
Check whether peripheral
equipments have strong interference
source
4
.
.Sound grounding or not
4
.
Check grounding line
E002
Over
current in
accelerated
running
1
.
Too fast acceleration
1
.
Increase acceleration time
2
.
Too low grid voltage
2
.
Check input power
3
.
The power of the SPD is too
low
3
.
Use bigger power SPD
E003
Over
current in
decelerated
running
1
.
Too fast deceleration
1
.
Increase deceleration time
2
.
The inertia torque of load is
too big.
2
.
Add proper dynamic braking
modules
3
.
The power of the SPD is too
low
3
.
Increase power of the SPD
E004
Over
current in
constant
speed
running
1
.
Saltation or abnormality
happens to load
1
.
Check the load or decrease the
saltation of the load
2
.
The grid voltage is too low
2
.
Check input power supply