PDM20 Series
- 47 -
Fault
code
Fault type
Possible reasons
Solution
4
.
Overload
4
.
Use bigger power SPD
E011
Motor
overload
1
.
The grid voltage is too low
1
.
Check grid voltage
2
.
Wrong setting to motor rated
current
2
.
Reset motor rated current
3
.
Motor stall or big changes to
load
3
.
Check the load and adjust torque
lifting capacity
4
.
Motor is too small
4
.
Use proper motor
E013
Output
phase loss
U,V,W phase loss output(or the
three phases of load is not
symmetrical)
1
.
Check output wiring
2
.
Check motor and cable
E014
Module
overheatin
g
1
.
Instant over current of SPD
1
.
Refer to over current solutions
2
.
Output three phases have
interphase or ground is short
circuit
2
.
Re-wiring
3
.
Air passage block or fan
broken
3
.
Dredge air passage or change fan
4
.
The environmental
temperature is too high
4
.
Decrease environmental
temperature
5
.
SPD wire or plugins loose
5
.
Check and re-connect
6
.
Power circuit irregularity
6
.
Seek for service