PDM20 Series
- 44 -
P1.10
Feedback broken line detection value
0.0
~
1.00
V
0.10
P1.11
Feedback broken line detection time
0.0
~
3600
s
5.0
Feedback broken line detection value: the detection value is relative to input signal
voltage. System keeps detecting PID feedback value. When feedback value is
smaller than or equal to feedback broken line detection, system starts detection
timing. When detection timing exceeds feedback broken line detection time,
system will report PID feedback broken line fault.
P1.12 Motor rated power
0
~
4.0
kW
Set according to models
P1.13 Motor rated frequency
0.01
~
60.00
Hz
Set according to models
P1.14 Motor rated speed
0
~
36000
rpm
Set according to models
P1.15 Motor rated voltage
0
~
280
V
Set according to models
P1.16
Motor rated current
0.1
~
40
A
Set according to models
Please set according to parameters of the motor nameplate.
To guarantee control performance, please configure motor according to standard
adaptive motor of drives. If there is big difference between motor power and
standard adaptive motor, control performance of drives will decrease obviously.