P0.08 PID sleep choices
0
~
2
2
0
:
Sleep invalid
1
:
Sleep mode 1
2
:
Sleep mode 2
P0.09
PID sleep detection
delay
0.0
~
120.0
s
1.0
In small water consumption, if
sleeping is slow or it can’t sleep,
make the value smaller; if it sleeps
in advance or it starts and stops
frequently, make the value bigger.
P0.10
PID wakeup detection
delay
0.0
~
120.0
s
1.0
PID wakeup detection delay
P0.11
PID sleep low level hold
frequency
0.00
~
60.00
Hz
35.00
PID runs at sleep low level hold
frequency. After the time of P0.12,
PID sleeps.
P0.12
Running time at PID
low level hold
frequency
0.00
~
3600
s
3.0
P0.13
PID sleep deviation
pressure
0.0
~
P0.01
bar
0.1
If feedback pressure is in sleep
deviation range, start sleeping
treatment.