PDM20 Series
- 39 -
P0.21
Set value of high
pressure alarm
0.0
~
P0.03
bar
8.0 When feedback pressure is bigger
than or equal to the set value, after
the delay of P0.22, it alarms and
stops.
P0.22
Detection time of
high pressure alarm
0.0
~
200.0
s
3.0
P0.23
Set value of low
pressure alarm
0.0
~
P0.21
bar
0.0
When feedback pressure is smaller
than the set value, after the delay of
P0.24, it alarms and stops. This
function is invalid when it is set to
0.
P0.24
Detection time of
low pressure alarm
0.0
~
200.0
s
3.0
The SPD will compare P0.21 and P0.23 according pipe network pressure fed back
by sensor. If pressure is abnormal, it will stop and alarm automatically to protect
pipe network system.
P0.25
Water shortage
protection
00
~
11
10
Ones
:
judge water shortage
according to frequency, current
0:OFF
1:ON
Tens
:
judge by pressure
0:OFF
1:ON
P0.26
Water shortage fault
detection threshold
0.0
~
P0.00
bar
0.5
It judges water shortage only when
feedback pressure is smaller than
the set value.
P0.27
Water shortage
protection detection
frequency
0
~
60.00
Hz
45.00
It is valid when P0.25 = 01.
Comparison frequency of water
shortage judgment.
P0.28
Current percentage of
water shortage
protection detection
80
~
300.0
%
150.0
It is valid only whenP0.25=01.
Percentage of motor rated current.
P0.29
Water shortage
protection detection
time
0
~
900.0
s
20.0
Summary of Contents for PDM20 series
Page 1: ...PDM20 Smart Mini Pump Drive User Manual Version Code PDM20 EN 60200256 1612 ...
Page 12: ...PDM20 Series 11 Example Modify P0 02 from 0 to 1 Remarks 0 1MPa 100kPa 1bar 1kgf cm2 ...
Page 14: ...PDM20 Series 13 2 3Dimensions Unit mm 136 116 176 158 114 105 124 138 ...
Page 59: ...PDM20 Series 58 V1 1 Inverter ...