Chapter 12: Constant List
Firmware – S2011 and S3012
Revision: 1 (9/98)
88
© Saftronics, Inc.
Table 27
Constant List (Continued)
Constant
Function Name
Description
Factory
Setting
n082
Output phase loss detection level
(SPO)
Unit
:
1%
Setting range :
0 to 100%
0%
n083
Output phase loss detection delay time
(SPO)
Unit
:
0.1 seconds
Setting range :
0.0 to 2.0 seconds
0.2 seconds
n084
PID selection (same as PID LED)
0
:
PID disabled
1
:
PID enabled (Deviation is D-controlled)
2
:
PID with feed forward (Feedback value is D-controlled)
3
:
PID with feed forward (Feedback is reversed characteristics)
0
n085
Feedback calibration gain (PID)
Unit
:
0.01
Setting range :
0.00 to 10.00
1.00
n086
Proportional gain (PID)
Unit:
:
0.1
Setting range :
0.0 to 10.0
1.0
n087
Integral time (PID)
Unit
:
0.1 seconds
Setting range :
0.0 to 100.0 seconds
10.0
seconds
n088
Derivative time (PID)
Unit
:
0.1 seconds
Setting range :
0.0 to 100.0 seconds
0.00
seconds
n089
Offset (PID)
Unit
:
1%
Setting range :
−
109 to 109%
0%
n090
Limit of integral value (PID)
Unit
:
1%
Setting range :
0 to 109%
100%
n091
Output lag filter time (PID)
Unit
:
0.1 seconds
Setting range :
0.0 to 2.5 seconds
0.0 seconds
n092
Feedback loss detection (PID)
0
:
Detection is disabled
1
:
Detection is enabled
0
n093
Feedback loss detection level(PID)
Unit
:
1%
Setting range :
0 to 100%
0%
n094
Feedback loss detection delay time
(PID)
Unit
:
0.1 seconds
Setting range :
0.0 to 25.5 seconds
1.0 seconds
n095
Energy Saving selection
(same as kWsav LED
0
:
Energy Saving is disabled
1
:
Energy Saving is enabled
0
n096
Energy Saving gain K2
Unit
:
0.01 (0.1 for 100.0 or above)
Setting range :
0.00 to 655.0
kVA
dependent
n097
Energy Saving voltage lower limit at
60Hz
Unit
:
1%
Setting range :
0 to 120%
50%
n098
Energy Saving voltage lower limit at
6Hz
Unit
:
1%
Setting range :
0 to 25%
12%
n099
Time of average k W (Energy Saving)
Unit
:
1 = 25ms
Setting range :
1 to 200
1
n100
Voltage limit of tuning (Energy Saving)
Unit
:
1%
Setting range :
0 to 100%
0%
n101
Step voltage of tuning at 100% output
voltage (Energy Saving)
Unit
:
0.1%
Setting range :
0.1 to 10.0%
0.5%
n102
Step voltage of tuning at 5% output
voltage (Energy Saving)
Unit
:
0.1%
Setting range :
0.1 to 10.0%
0.2%
n103
MEMOBUS time over detection
0
:
Time over detection is disabled
1
:
Time over detection is enabled
1
n104
MEMOBUS stop method at
communication error (CE)
(Setting)
(Stop Method)
0
:
Ramp to stop
−
Decel 1 (fault)
1
:
Coast to stop (fault)
2
:
Ramp to stop
−
Decel 2 (fault)
3
:
Continue operation (alarm)
1
n105
MEMOBUS frequency reference unit
(Setting)
(Frequency Unit)
0
:
0.1Hz / 1
1
:
0.01Hz / 1
2
:
100% / 30000
3
:
0.1% / 1
0
n106
MEMOBUS slave address
Unit
:
1
Setting range :
0 to 31
0
n107
MEMOBUS BPS selection
(Setting)
(BPS Rate)
0
:
2400 BPS
1
:
4800 BPS
2
:
9600 BPS
2
n108
MEMOBUS parity selection
(Setting)
(BPS Rate)
0
:
No parity
1
:
Even parity
2
:
Odd parity
1