Chapter 12: Constant List
Firmware – S2011 and S3012
Revision: 1 (9/98)
84
© Saftronics, Inc.
12.1
Constant List
Table 27
Constant List
Constant
Function Name
Description
Factory
Setting
n001
Password
0
: n001 read and set, n002 to n108 read only
1 : n001 to n034 read and set, n035 to n108 read only
2 : n001 to n049 read and set, n050 to n108 read only
3 : n001 to n108 read and set
4 : Not used
5 : Not used
6 : 2-wire initialization
−
reset (Japanese standard)
7 : 3-wire initialization
−
reset (Japanese standard)
8 : 2-wire initialization
−
reset (U.S. specifications)
9 : 3-wire initialization
−
reset (U.S. specifications)
10 : 2-wire initialization – reset (European specifications)
11 : 3-wire initialization – reset (European specifications)
1
n002
Operation mode selection
(Setting)
(Operation)
(Reference)
0
:
Operator
Operator
1
:
Terminal
Operator
2
:
Operator
Terminal
3
:
Terminal
Terminal
4
:
Operator
Serial com
5
:
Terminal
Serial com
6
:
Serial com
Serial com
7
:
Serial com
Operator
8
:
Serial com
Terminal
3
n003
Input voltage
Unit
:
0.1V
Setting range :
150.0 to 255.0V (510V for 400V units)
200.0V
(400.0V)
n004
Stopping method selection
0
: Deceleration to stop
1
: Coast to stop
2
: Coast to stop with timer 1
3
: Coast to stop with timer 2
0
n005
Power rotation
0
: CCW
1
: CW
0
n006
Reverse run prohibit
0
: Reverse run enabled
1
: Reverse run disabled
0
n007
LOCAL/REMOTE key function
0
: Disabled
1
: Enabled
1
n008
Stop key function
0
: STOP key is effective when operated from Digital Operator
1
: STOP key is always effective
1
n009
Frequency reference setting method
from Digital Operator
0
: ENTER key not used
1
: ENTER key used
1
n010
V/f pattern selection (same as V/f
LED)
0 to E
:
15 preset V/f patterns
F
:
Custom V/f pattern with voltage limit
FF
:
Custom V/f pattern without voltage limit
1
n011
Motor rated voltage
(same as Vmtr LED)
Unit
:
0.1V
Setting range :
150.0 to 255.0V (510 V for 400V units)
200.0V
n012
Maximum output frequency
Unit
:
0.1Hz
Setting range :
50.0 to 400.0Hz
60.0 Hz
n013
Maximum voltage
Unit
:
0.1V
Setting range :
0.1 to 255.0V (510 V for 400V units)
200.0V
n014
Maximum voltage output frequency
Unit
:
0.1HZ
Setting range :
0.2 to 400.0V
60.0Hz
n015
Middle output frequency
Unit
:
0.1Hz
Setting range :
0.1 to 399.9Hz
3.0Hz
n016
Middle frequency voltage
Unit
:
0.1V
Setting range :
0.1 to 255.0V (510V for 400V units)
15.0V
n017
Minimum output frequency
Unit
:
0.1Hz
Setting range :
0.1 to 10.0Hz
1.5Hz
n018
Minimum output frequency voltage
Unit
:
0.1V
Setting range
0.1 to 50.0V
10.0V
n019
Acceleration time 1
(same as Accel LED)
Unit
:
0.1 seconds (1 seconds for 1000 seconds and above)
Setting range :
0.0 to 3600 seconds
10.0
seconds
n020
Deceleration time 1
(same as Decel LED)
Unit
:
0.1 sec (1 seconds for 1000 seconds and above)
Setting range :
0.0 to 3600 seconds
10.0
seconds
n021
Acceleration time 2
Unit
:
0.1 seconds (1 seconds for 1000 seconds and above)
Setting range :
0.0 to 3600 seconds
10.0
seconds
efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor