Chapter 13: Digital Operator Monitor Display
Firmware – S2011 and S3012
Revision: 1 (9/98)
93
© Saftronics, Inc.
Table 28
Digital Operator Monitor Display (Continued)
LED
Name
Description
No.
Contents
U
−
09
Maximum 4 faults can be monitored.
U
−
10
Lower 4 digits of PROM number can be monitored.
Elapsed time can be monitored as follows.
U
−
11
U
−
12
X X X X X X
Elapsed time (in units of 1 hour)
U-10 (lower 4 digits)
U-11 (upper 2 digits)
Maximum 279,620 hours
Montr
Monitor
U
−
13
PID feedback can be monitored. Display unit depends on the setting of n024.
Accel
Acceleration time 1
Acceleration time 1 (n019) can be set/read in units of 0.1 seconds (1 seconds for 1000 sec and
above).
Decel
Deceleration time 1
Deceleration time 1 (n020) can be set/read in units of 0.1 seconds (1 seconds for 1000 sec and
above).
Vmtr
Motor rated voltage
Motor rated voltage (n011) can be set during stop.
V/f
V/f pattern selection
V/f pattern selection (n010) can be set during stop.
Fgain
Frequency reference
gain
Frequency reference gain (n046) can be set during stop.
Fbias
Frequency reference
bias
Frequency reference bias (n047) can be set during stop.
FLA
Motor rated current
Motor rated current (n032) can be set during stop.
PID
PID selection
PID selection (n084) can be set during stop.
kWsav
Energy Saving
selection
Energy Saving selection (n095) can be set during stop.
PRGM
PRGM mode
Constants can be set/read.