Chapter 9: Specifications
Firmware – S2011 and S3012
Revision: 1 (9/98)
72
© Saftronics, Inc.
9.1
Standard Specifications
Table 23
200 V Class Specifications
Series
FP5/GP5
Models
FP5/GP5
23P7
25P5
27P5
2011
2015
2018
2022
2030
2037
2045
2055
2075
Maximum Applicable Motor
Output *(kW)
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
Inverter Capacity (kVA)
6.7
9.5
13
19
24
30
37
50
61
70
85
110
Rated Output Current (A)
17.5
25
33
49
64
80
96
130
160
183
224
300
Maximum Output Voltage
3-Phase, 200/208/220/230 V (Proportional to input voltage)
Output
Characteristics
Rated Output Frequency
Up to 400 Hz available by programming
Rated Input Voltage and
Frequency
3-Phase 200/208/220 V 50 Hz
200/208/220/230 V 60 Hz
Allowable Voltage
Fluctuation
+
10%,
−
15%
Power
Supply
Allowable Frequency
Fluctuation
±
5%
Control Method
Sine wave PWM
Frequency Control Range
0.1 to 400 Hz
Digital Command: 0.01% (
−
10
°
C to
+
40
°
C)
Frequency Accuracy
Analog Command: 0.1% (25
°
C
±
10
°
C)
Digital Operator reference: 0.1 Hz
Frequency Resolution
Analog reference: 0.1 Hz
Output Frequency
Resolution
0.1 Hz
Overload Capacity
150% of rated output current for 1 minute
120% of rated output current for 1 minute
Frequency Setting Signal
0 to
+
10 V (20k
Ω
), 4 to 20 mA (250
Ω
)
Accel/Decel Time
0.0 to 3600 sec (Accel/decel time setting independently)
Braking Torque
Approximately 20%
(Approximately 125% with Braking Resistor)
Approximately 20%
(Braking Resistor cannot be mounted)
Control Characteristics
Number of V/f Patterns
15 preset V/f patterns, 1 custom V/f with voltage limit, 1 custom without voltage limit
Motor Overload
Protection
Protected by electronic Thermal Overload Relay
Instantaneous
Overcurrent
Motor coasts to a stop at approximately 200% of
Inverter rated current.
Motor coasts to a stop at approximately 180% of
Inverter rated current.
Overload
Motor coasts to a stop after 1 minute at 150% of
rated output current.
Motor coasts to a stop after 1 minute at 120% of
rated output current.
Overvoltage
Motor coasts to a stop if converter output voltage exceeds 410 V.
Undervoltage
Motor coasts to a stop if converter output voltage drops to 190 V or below.
Momentary Power Loss
Immediately stop by 15 ms and above momentary power loss. (Factory setting)
Continuous operation during power loss less than 2 seconds is equipped as standard.
Heatsink Overheat
Protected by thermistor.
Stall Prevention
Stall Prevention during accel/decel and constant speed operation.
Ground Fault
Protected by electronic circuit.
Protective Functions
Power Charge Indication
CHARGE LED stays ON until bus voltage drops below 50 V.
Ambient Temperature
−
10
°
C to
+
40
°
C (Enclosed wall-mounted type)
−
10
°
C to
+
45
°
C (Open chassis type)
Humidity
90% RH or less
Storage Temperature
−
20
°
C to
+
60
°
C
Locatioan
Indoor (protected from corrosive gases and dust)
Elevation
1000 meters or less
Environment
Vibration
9.81m/s
2
(1G) at 10 to less than 20 Hz, up to 1.96m/s
2
(0.2G) at 20 to 50 Hz.
∗
Based on a Saftronics standard 4-pole motor for maximum applicable motor output.
efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor