Operating manual - ChillPAC and LP ChillPAC Mk 3
010823 en 2021.06
59/68
1.
Open the tightening screw (pos. 1) on the meta glass connector and the fixing screw (pos. 2),
see Fig. 27.
2.
Fit it carefully on the process connector. The loose screw (pos. 1) gives way for the trapped air
so the signal converter can be installed. It should be pressed down carefully, yet with some
force, to fit over the o-ring.
3.
Now tighten both screws carefully according to the AKS instructions.
4.
When power is connected, and the screen is starting up, do a quick set-up according to the in-
structions in Fig. 28.
Enter menu system
Enter QUICK SETUP
Unit change at
distance/level
readout:
m, cm, mm, in, ft
Change between:
Distance*
Level**
Output (%)***
Output (mA)****
*
AKS 4100
Connect the device to the power supply
Note:
The signal converter can be programmed with or without mechanical process
connector assembled.
To configure the signal converter, a HMI display is always needed.
• Connect the device to the power supply
(see the section "Electrical installation/
connection").
• Press 3 times.
• Press
• Press or to select between SINGLE,
COAXIAL D14 and COAXIAL D22. Choose
D22
and press
• Press
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
D22
• Press to change the PROBE LENGTH.
Press to change the position of the
cursor.
Press to decrease the value or to
increase the value.
Press
• Press to change of SCALE 4 mA.
Press to change the cursor position.
Press to decrease the value or to
increase the value.
Press
• Press to change of SCALE 20 mA.
Press to change the cursor position.
Press to decrease the value or to
increase the value.
Press
• Wait for QUICK SETUP to complete.
Count down from 8 sec.
• Press
• Press or to select between
STORE NO or STORE YES.
Press
Default screen appears:
QUICK SETUP completed
AKS 4100
CO2?
YES NO
AKS 4100
SCALE 4 mA
210 mm
AKS 4100
SCALE 20 mA
00060 mm
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
XXX mm
AKS 4100
1.0.0
QUICK START
AKS 4100
PROBE LENGTH
00280 mm
AKS 4100
QUICK SETUP ?
YES NO
Fig. 28: Quick set-up of AKS 4100 280 mm