Fig. 19: Oil recovery pot
3.2.10
Automatic oil return from the oil separator
The oil collected in the oil separator is returned to the compressor by a timer-operated solenoid valve.
The timer can be adjusted in the UniSAB III controller.
3.2.11
Alarm for high level in the evaporator
The ChillPAC and the LP ChillPAC (external condenser) both have a level switch.
If the R717 liquid level becomes too high in the evaporator, the level switch will stop the compressor.
This will protect the compressor against liquid hammering. See subsection
for correct
charge.
Note: The liquid level must never be visible in the inspection glass.
DN2
5
1
NO
NC
2
3
Oil
Oil / R-717
Discharge gas