Operating manual - ChillPAC and LP ChillPAC Mk 3
010823 en 2021.06
63/68
Fig. 37
Change to ‘STORE YES’ with
Arrow down
(no. 3) or
Arrow up
(no. 4) and
Confirm
(no. 2).
You will then return to the standard display and the AKS 4100 is now running with optimised
parameters.
Note:
After changing the parameters, do NOT run a quick set-up. If you do so, you will need to fill in the
parameters again.
If you make a new set-up, please fill in the set-up parameters in the table, and add them to your
logbook.
Installation
date:
Filled in values
Recommended
values
AKS 4100
280 mm
Probe
D22
CO
2
NO
Probe length
280 mm
4 mA scale
210 mm
20 mA scale
60 mm
Gas constant 2.5.3
See the list in Fig. 39
(heat pump: approx. 1.2–
1.4)
Blocking distance 2.3.2
0 mm
Time constant 2.3.3
1 sec.
Level threshold 2.5.7
150
Full area 4.1.1
0 mm
Empty area 4.1.2
260 mm
ICAD
ICAD speed i04
100%
UniSAB
Set point regulation
20% – 25%
Table 3: List of values for logbook
Note:
A level set point is highly recommended.
Be aware of proper functioning of the AKS 4100 280 mm.
Heat pump application can only be provided if the mentioned recommendations are followed,
and the level set point in UniSAB III is set between 20 and 25%.