All other necessary settings are done at the boiler control. A boiler frost protection
function is not activated by the controller. This is done independently by the boiler
control.
Sensor connection:
Condensing boilers with MCBA boiler controls have a connection for an outdoor and
hot water tank sensor by Honeywell. In combination with the controller series
THETA, the outdoor and hot water sensors of the standard unit as well as the
Honeywell sensors can be used. It is important to make sure that the controller
sensors are connected to the standard unit and the Honeywell sensors are
connected to the boiler control.
The following applies to both the outdoor as well as the tank sensors:
• If a sensor is connected to the standard unit, this sensor value is used for control.
• If no sensor is connected to the standard unit, a check takes place, if the
Honeywell sensor is connected to the boiler control. If so, then this sensor value
is automatically used for control.
• If a sensor is neither connected to the standard unit nor to the boiler control, an
error message is sent.
8.1.20
Heat generator forced dissipation
Forced discharge
Forced discharge to the subsequent heating circuits should take place when the
DHW maximum temperature is exceeded (necessary because e.g. pellet boilers are
controlled in the same way as single stage H-GEN).
Function:
The function description should be the same as for the buffer forced dissipation.
• If the current temperature of the heat generator exceeds the heat generator
maximum temperature limit, forced dissipation according to the setting of this
parameter will take place in
the DHW circuit or
the heating circuits or
a buffer tank
• The heating circuits adjust to thier maximum temperature.
• If the temperature in the heat generator decreases to 2 K under the heat
generator maximum temperature limit, forced dissipation is stopped.
• Forced dissipation is effective for multiple controllers (BUS system).
Effective parameters via MCBA for DHW mode:
Parameter
Designation:
DHW
NIGHT
Hot water economy temperature
LEGION.PROT.
DAY
Day for legionella-protection
03
Time for legionella protection
04
Temperature for legionella protection
05
Type of DHW temperature measurement
06
DHW maximum temperature limit
07
DHW operating mode
08
DHW tank discharge protection
09
Boiler parallel shift during DHW charging
10
DHW switching differential
Operation:
Note on operation
Key / parameter tree
Parameter
H-GEN forced dissipation
HEAT GENER.
PARAMETER 29
Summary of Contents for Controller Series
Page 2: ......
Page 8: ...EbV Product documentation THETA NORM UNIT VI...
Page 10: ...EbV Product documentation THETA NORM UNIT 1 2...
Page 16: ...EbV Product documentation THETA NORM UNIT 2 6...
Page 18: ...EbV Product documentation THETA NORM UNIT 3 2...
Page 20: ...EbV Product documentation THETA NORM UNIT 4 2...
Page 70: ...EbV Product documentation THETA NORM UNIT 5 50...
Page 78: ...EbV Product documentation THETA NORM UNIT 6 8...
Page 162: ...EbV Product documentation THETA NORM UNIT 10 10...
Page 170: ...EbV Product documentation THETA NORM UNIT 11 8...