EbV
Product documentation THETA NORM/UNIT
5-43
5.6.3
DOMESTIC HOT WATER (Type ..B..) Level
Parameter
Designation
Setting range / Setting values
Fac
tory
set
tin
g
s
Indiv
idua
l
set
tin
g
Link
DHW NIGHT
Hot water economy
temperature
10 °C ... Hot water temperature
40 °C
LEGION.PROT.
DAY
Day for legionella protection
OFF No
legionella
protection
Mo...SuLegionella protection on the specified
weekday
ALL
daily legionella protection
OFF
03
Time for legionella
protection
00:00...23:50 hour
02:00
04
Temperature for legionella
protection
10 °C ... DHW maximum temperature
65 °C
05
Type of DHW temperature
measurement
1 DHW
temperature
sensor
2
DHW temperature controller (thermostat)
1
06
DHW- temperature limit
20 °C ... maximum boiler temperature
65 °C
07
DHW operating mode
1 parallel
mode
2 Priority
mode
3 Conditional
priority
4
Weather responsive parallel mode
5
Priority mode with intermediate heating
6 Priority-separation
circuit
7
External operation
2
08
DHW tank discharge
protection
OFF
- No discharge protection
ON
- Discharge protection activated
ON
09
Boiler parallel shift during
DHW charging
0 ... 50 K;
Difference between the DHW charging temperature
and DHW setpoint
15 K
10
DHW switching differential
2 ... 20 K;
Amount of DHW switching differential, symmetrical
to the DHW setpoint
5 K
11
DHW charging pump
Extended running time
0 ... 60 Min
5 Min
12
Time programm circulation
pump
AUTO - Active DHW time program
1
- P1, direct circuit
2
- P2, direct circuit
3
- P3, direct circuit
4
- P1, mixed circuit 1
5
- P2, mixed circuit 1
6
- P3, mixed circuit 1
7
- P1, mixed circuit 2
8
- P2, mixed circuit 2
9
- P3, mixed circuit 2
10
- P1, DHW circuit
11
- P2, DHW circuit
12
- P3, DHW circuit
AUTO
13
Economy intervall - cir.
pump (no pulse period)
0 Min ... Setting parameter 14,
time of circulation pump stop)
5 Min
14
Economy intervall - cir.
pump
(Period duration)
10... 60 Min
Duration = shutdown time + operating time
20 Min
Summary of Contents for Controller Series
Page 2: ......
Page 8: ...EbV Product documentation THETA NORM UNIT VI...
Page 10: ...EbV Product documentation THETA NORM UNIT 1 2...
Page 16: ...EbV Product documentation THETA NORM UNIT 2 6...
Page 18: ...EbV Product documentation THETA NORM UNIT 3 2...
Page 20: ...EbV Product documentation THETA NORM UNIT 4 2...
Page 70: ...EbV Product documentation THETA NORM UNIT 5 50...
Page 78: ...EbV Product documentation THETA NORM UNIT 6 8...
Page 162: ...EbV Product documentation THETA NORM UNIT 10 10...
Page 170: ...EbV Product documentation THETA NORM UNIT 11 8...