Product documentation THETA NORM/UNIT
5-44
5.6.4
Selection levels unmixed circuit / mixed circuit 1 / mixed circuit 2
* only OEM
** only if remote unit is room controller (PARAMETER 04 = RC)
Parameter
Designation
Setting range / Setting values
Fac
tory
set
tin
g
s
Indiv
idua
l
set
tin
g
Link
RED.HEATING
Type of reduced mode
ECO - Switch-off mode (frost protection)
RED
- Reduced mode
ECO
HEAT.
SYSTEM
Heating system (exponent)
1,00 ... 10,00
HC
=1,30
MC
=1.10
03
Room influence (with room
unit )
OFF
Room sensor deactivated
1
Room sensor enabled
2
Room sensor enabled, operation for
remote unit disabled
3
only display mode (room temp.)
OFF
04
Room factor
OFF, 10 ... 500 %, RC (only room control)
OFF
05
Adaptation heating curve
OFF, ON
OFF
06
Optimmization (start)
OFF, 1 ... 8 h
OFF
07
Heating limit
OFF, 0.5 … 40 K
OFF
08
Room frost protection limit
5 ... 30 °C
10 °C
09
Room thermostat function
OFF, 0,5 ... 5 K
OFF
10
Outdoor sensor assignment
(only if VI n = outdoor
sensor 2)
0
Control to mean value of OS 1 + OS 2
1
Control to OS 1
2
Control to OS 2
0
11
Constant temperature
setpoint
10... 95 °C (only if output is set at constant-
control (CC))
20 °C
12
Minimum flow temperature
limit
10 °C ...
Setting value maximum temperature
limit (Parameter 13)
20 °C
13
Maximum temperature limit
Minimum temperature limit (Parameter 12) ...
Setting value maximum temperature limit heat
generator
75 °C
14
Heating circuit parallel shift
-5 ... 20 K
HC=0
MC=4
15
Heating pump (MC1, MC2)
extended running time
0 ... 60 Min
5 Min
16
Compos. floor drying
function (only if the circuit is
enabled exclusively)
OFF
Function switched off
1 Function
heating
2
Occupation suitable heating
3
Function and occupation suitable heating
OFF
18*
P-band Xp
1 ... 50 %/K
5,0
19*
Sample time Ta
1 ... 600 s
20
20*
I-band Tn
1 ... 600 s
180
21*
Actuator Running Time
10 ... 600 s
120
22*
Limit stops function actuator
1
Continuous actuator signal at limit stop
2
Actuator signal suppressed at limit stop
(Actuator de-energized)
2
23**
P-band room control
1...100 %/K
8
24**
I-band Tn room control
5...240 min.
35
Summary of Contents for Controller Series
Page 2: ......
Page 8: ...EbV Product documentation THETA NORM UNIT VI...
Page 10: ...EbV Product documentation THETA NORM UNIT 1 2...
Page 16: ...EbV Product documentation THETA NORM UNIT 2 6...
Page 18: ...EbV Product documentation THETA NORM UNIT 3 2...
Page 20: ...EbV Product documentation THETA NORM UNIT 4 2...
Page 70: ...EbV Product documentation THETA NORM UNIT 5 50...
Page 78: ...EbV Product documentation THETA NORM UNIT 6 8...
Page 162: ...EbV Product documentation THETA NORM UNIT 10 10...
Page 170: ...EbV Product documentation THETA NORM UNIT 11 8...