Product documentation THETA NORM/UNIT
8-47
Operating mode 6 – Discharge control to heat generator
System hydraulics:
This hydraulic layout is used when an alternative-energy buffer tank is added to an
existing system. In such systems there are often existing unit boilers with integrated
DHW tank and DHW loading.
All heat requests are sent to the heat generator.
When the buffer tank can cover the energy demand, the heat generator nominal
temperature is maintained by the buffer, via BULP (PLP), instead of the burner.
In this way the heat generator always operates at its nominal temperature and can
not be exposed to excessive buffer temperatures.
See the table below for detailed correlations.
Buffer operating mode
1
2
3
4
5
6
Buffer request from
HC/DHW
HC
HC/DHW
HC
HC
---
H-GEN request from
BUFFER
BUFFER/
DHW
BUFFER
BUFFER/
DHW
BUFFER/
DHW
HC/DHW
Buffer control type
Charge
Charge
Discharge 1
Discharge 1
Charge
Discharge 2
Buffer start-up protection acts on
HC/DHW
HC
HC/DHW
HC
HC
---
Buffer discharge protection
X
X
---
---
X
---
Buffer frost protection monitoring
X
X
---
---
X
---
Buffer minimum temperature
monitoring
X
X
---
---
X
---
Buffer maximum temperature
monitoring
X
X
X
X
X
X
Buffer forced dissipation into
HC/DHW
HC
HC/DHW
HC
HC
HC/DHW
Buffer skimming function
X
X*
---
---
X*
---
Loading temperature control from
HC/DHW
HC
---
---
HC
---
H-GEN start-up protection on
BULP
X
X
---
---
X
---
Function BULP without request
OFF
OFF
OFF
OFF
OFF
OFF
Function BULP for manual
operation
ON
ON
OFF
OFF
ON
OFF
Function BULP for sensor defect
ON
ON
OFF
OFF
ON
OFF
Function BULP for heat
generator disabled
---
---
ON
ON
---
---
Function BULP if H-GEN not
available and buffer start-up
protection is active**
---
---
OFF
OFF
---
---
Function BULP if H-GEN
available and buffer start-up
protection is not active**
---
---
ON
ON
---
---
Effect of H-GEN start-up
protection on
BULP
DHW/BULP
HC/DHW
HC/DHW
BULP
HC/DHW
Tank discharge protection / H-
GEN in system
BULP
H-GEN
H-GEN
H-GEN
H-GEN
H-GEN
Tank discharge protection / no H-
GEN in system
BULP
H-GEN
BULP
H-GEN
H-GEN
H-GEN
OS
BU
BULP
BS
HC-P
VF1
VF2
MC1
MC2
SOL-P
DHWS
BU
Buffer
Heat
generator
Domestic hot
water
tank
Summary of Contents for Controller Series
Page 2: ......
Page 8: ...EbV Product documentation THETA NORM UNIT VI...
Page 10: ...EbV Product documentation THETA NORM UNIT 1 2...
Page 16: ...EbV Product documentation THETA NORM UNIT 2 6...
Page 18: ...EbV Product documentation THETA NORM UNIT 3 2...
Page 20: ...EbV Product documentation THETA NORM UNIT 4 2...
Page 70: ...EbV Product documentation THETA NORM UNIT 5 50...
Page 78: ...EbV Product documentation THETA NORM UNIT 6 8...
Page 162: ...EbV Product documentation THETA NORM UNIT 10 10...
Page 170: ...EbV Product documentation THETA NORM UNIT 11 8...