EbV
Product documentation THETA NORM/UNIT
5-36
5.4.5.2
Legionella protection day
Factory preset:
OFF
Setting range:
OFF, MO...SU, ALL
Setting values:
OFF:
The legionella protection function is not active.
MO...SU:
The legionella protection is activated on the selected
weekday at the Llegionella protection time set by the heating
specialist with a different parameter.
ALL:
The legionella protection function is activated every day
at the Legionella protection time.
Function:
This parameter serves to prevent a legionella outbreak in the hot water tank and is
activated on the selected weekday or every day at 02:00 hrs. If the DHW temperature
is below 65°C, the hot water tank is reloaded.
Note:
If a DHW thermostat is used to determine the water heater temperature, this
parameter is skipped.
5.4.6
Unmixed Circuit / Mixed Circuit 1 / Mixed Circuit 2 Menu
This level comprises all parameters which are necessary to program the heating
circuits with the exception of the time programs. A maximum of 1 unmixed circuit and
2 mixed circuits (mixed circuit 1 and mixed circuit 2) are available per controller as
heating circuits.
The heating circuit parameters described below are available for each heating circuit
and are to be set separately.
Summary of Contents for Controller Series
Page 2: ......
Page 8: ...EbV Product documentation THETA NORM UNIT VI...
Page 10: ...EbV Product documentation THETA NORM UNIT 1 2...
Page 16: ...EbV Product documentation THETA NORM UNIT 2 6...
Page 18: ...EbV Product documentation THETA NORM UNIT 3 2...
Page 20: ...EbV Product documentation THETA NORM UNIT 4 2...
Page 70: ...EbV Product documentation THETA NORM UNIT 5 50...
Page 78: ...EbV Product documentation THETA NORM UNIT 6 8...
Page 162: ...EbV Product documentation THETA NORM UNIT 10 10...
Page 170: ...EbV Product documentation THETA NORM UNIT 11 8...