VLT
®
8000 AQUA
■
Technical data, line supply 3 x 380 - 480 V
According to international requirements
VLT type
8016
8022
8027
8032
8042
Output current
I
VLT,N
[A] (380-440 V)
24.0
32.0
37.5
44.0
61.0
I
VLT, MAX
(60 s) [A]
(380-440 V)
26.4
35.2
41.3
48.4
67.1
I
VLT,N
[A] (441-480 V)
21.0
27.0
34.0
40.0
52.0
I
VLT, MAX
(60 s) [A]
(441-480 V)
23.1
29.7
37.4
44.0
57.2
Output power
S
VLT,N
[kVA] (400 V)
17.3
23.0
27.0
31.6
43.8
S
VLT,N
[kVA] (460 V)
16.7
21.5
27.1
31.9
41.4
Typical shaft output
P
VLT,N
[kW]
11
15
18.5
22
30
Typical shaft output
P
VLT,N
[HP]
15
20
25
30
40
Max. cable cross-section to
motor and DC-bus, IP 20
16/6
16/6
16/6
35/2
35/2
Max. cable cross-section to
motor and DC-bus, IP 54
[mm
2
]/[AWG]
2) 4)
16/6
16/6
16/6
16/6
35/2
Min. cable cross-section to
motor and DC-bus
[mm
2
]/[AWG]
2) 4)
10/8
10/8
10/8
10/8
10/8
Max. input current
I
L,N
[A] (380 V)
24.0
32.0
37.5
44.0
60.0
(RMS)
I
L,N
[A] (480 V)
21.0
27.6
34.0
41.0
53.0
Max. cable cross-section
power, IP 20
16/6
16/6
16/6
35/2
35/2
Max. cable cross-section
power, IP 54
[mm
2
]/[AWG]
2) 4)
16/6
16/6
16/6
16/6
35/2
Max. pre-fuses
[-]/UL
1)
[A]
63/40
63/40
63/50
63/60
80/80
Line contactor
[Danfoss type]
CI 9
CI 16
CI 16
CI 32
CI 32
Efficiency at rated frequency
0.96
0.96
0.96
0.96
0.96
Weight IP 20/NEMA 1
[kg/lbs]
21/46
21/46
22/49
27/60
28/62
Weight IP 54/NEMA 12
[kg/lbs]
41/90
41/90
42/93
42/93
54/119
Power loss at max. load.
[W]
419
559
655
768
1065
Enclosure
IP 20/NEMA 1/ IP 54/NEMA 12
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m/100 ft shielded motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Max. cable cross section is the
maximum possible cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.
MG.80.A7.22 - VLT is a registered Danfoss trademark
36
Rosewood STP ST42 General (Operation and Maintenance Manual - Part 4:
Section 6.3 Manufacturers Manuals 6.3.33 Danfoss VLT Aquadrive 8000) Vendor Manual
QP Id: VM207
Active: 03/09/2013