All AFDs must be installed in a way that
ensures proper cooling.
Cooling
All units require a minimum space above and
below the enclosure.
Side by side/flange by flange
All AFDs can be mounted side by side/flange by flange.
d [mm/in]
Comments
Compact (all enclosure types)
VLT 8006-8011, 380-480 V
100/3.9
VLT 8002-8011, 525-600 V
100/3.9
Installation on a plane, vertical surface (no spacers)
VLT 8006-8032, 200-240 V
200/7.9
VLT 8016-8072 380-480 V
200/7.9
VLT 8102-8122 380-480 V
225/8.9
VLT 8016-8072 525-600 V
200/7.9
Installation on a plane, vertical surface (no spacers)
VLT 8042-8062, 200-240 V
225/8.9
VLT 8100-8300, 525-600 V
225/8.9
Installation on a plane, vertical surface (no spacers)
IP 54 filter mats must be changed when they are dirty.
VLT 8152-8352, 380-480 V
225/8.9
Installation on a plane, vertical surface (spacers can be used). IP 54
filter mats must be changed when they are dirty.