VLT
®
8000 AQUA
Programming
■
Inputs and outputs 300-328
In this parameter group, the
functions that relate to the
input and output terminals
of the AFD are defined.
The digital inputs (terminals
16, 17, 18, 19, 27, 29, 32
and 33) are programmed in
parameters 300-307.
The table below gives the options for programming
the inputs. The digital inputs require a signal of 0 or
24 V DC. A signal lower than 5 V DC is a logic ‘0
’
,
while a signal higher than 10 V DC is a logic ‘1
’
.
The terminals for the digital inputs can be
connected to the internal 24 V DC supply, or an
external 24 V DC supply can be connected.
The drawings in the next column show one Setup
using the internal 24 V DC supply and one Setup
using an external 24 V DC supply.
Switch 4, which is
located on the Dip
switch control card,
is used for separating the common potential of
the internal 24 V DC supply from the common
potential of the external 24 V DC supply. See
Electrical installation
.
Please note that when Switch 4 is in the OFF
position, the external 24 V DC supply is galvanically
isolated from the AFD.
Digital inputs
Terminal no.
16
17
18
19
27
29
32
33
parameter
300 301
302
303 304 305
306
307
Value:
No function
(NO OPERATION)
[0]
[0]
[0]
[0]
[0]
[0]
✭
[0]
✭
Reset
(RESET)
[1]
✭
[1]
[1]
[1]
[1]
Coasting stop, inverse
(COAST INVERSE)
[0]
Reset and coasting stop, inverse
(RESET & COAST INVERS)
[1]
Start
(START)
[1]
✭
Reversing
(REVERSE)
[1]
✭
Reverse and start
(START INVERSE)
[2]
DC-braking, inverse
(DC BRAKE INVERSE)
[3]
[2]
Safety interlock
(SAFETY INTERLOCK)
[3]
✭
Freeze reference
(FREEZE REFERENCE)
[2]
[2]
✭
[2]
[2]
[2]
Freeze output
(FREEZE OUTPUT)
[3]
[3]
[3]
[3]
[3]
Selection of Setup, lsb
(SETUP SELECT LSB)
[4]
[4]
[4]
Selection of Setup, msb
(SETUP SELECT MSB)
[4]
[5]
[4]
Preset reference, on
(PRESET REF. ON)
[5]
[5]
[6]
[5]
[5]
Preset reference, lsb
(PRESET REF. LSB)
[6]
[7]
[6]
Preset reference, msb
(PRESET REF. MSB)
[6]
[8]
[6]
Speed down
(SPEED DOWN)
[7]
[9]
[7]
Speed up
(SPEED UP)
[7]
[10]
[7]
Run permissive
(RUN PERMISSIVE)
[8]
[8]
[11]
[8]
[8]
Jog
(JOG)
[9]
[9]
[12]
✭
[9]
[9]
Data change lock
(PROGRAMMING LOCK)
[10] [10]
[13]
[10]
[10]
Pulse reference
(PULSE REFERENCE)
[11]
[14]
Pulse feedback
(PULSE FEEDBACK)
[11]
Hand start
(HAND START)
[11] [12]
[15]
[11]
[12]
Auto start
(AUTO START)
[12] [13]
[16]
[12]
[13]
Latched start
(LATCHED START)
[2]
Off stop
(OFF STOP)
[17]
[13]
[14]
Stop inverse
(STOP INVERSE)
[19]
[14]
[15]
Motor alternation
(MOTOR ALTERNATION)
[15]
Motor alternation
(MOTOR ALTERNATION)
[16]
Motor alternation
(MOTOR ALTERNATION)
[20]
Motor alternation
(MOTOR ALTERNATION)
[15]
Motor alternation
(MOTOR ALTERNATION)
[15]
✭
= factory setting. () = display text [] = value for use in communication via serial communication port