Rosemount Models 3144 and 3244MV Smart Temperature Transmitters
5-6
Temperature Limits
Humidity Limits
0–100% relative humidity
Turn-on Time
Performance within specifications less than 5.0 seconds after power is
applied to transmitter
Update Time
Approximately 0.5 seconds
Performance
Specifications
The Model 3144 and 3244MV transmitters maintain a specification
conformance of at least 3
σ
.
Accuracy
Refer to Table 5-1 on page 5-10.
Stability
±0.1% of reading or 0.1 °C, whichever is greater, for 24 months for RTDs
±0.1% of reading or 0.1 °C, whichever is greater, for 12 months for
thermocouples
5 Year Stability
±0.25% of reading or 0.25 °C, whichever is greater, for 5 years for RTDs
±0.5% of reading or 0.5 °C, whichever is greater, for 5 years for
thermocouples
Power Supply Effect
Less than ±0.005% of span per volt
RFI Effect
Worst case RFI effect is equivalent to the transmitter’s nominal
accuracy specification per Table 1 on page 13 when tested in accordance
with ENV 50140, 30 V/m, 80 to 1000 MHz, with unshielded cable.
Vibration Effect
Transmitters tested to the following specifications with no effect on
performance:
Self Calibration
The analog-to-digital measurement circuitry automatically
self-calibrates for each temperature update by comparing the dynamic
measurement to extremely stable and accurate internal reference
elements.
Operating
Storage
–40 to 185 °F (–40 to 85 °C)
–60 to 250 °F (–50 to 120 °C)
–40 to 185 °F (–20 to 85 °C)
for transmitters with optional
LCD meter
–50 to 185 °F (–45 to 85 °C)
for transmitters with optional
LCD meter
Frequency
Acceleration
10–60 Hz
0.21 mm peak displacement
60–2000 Hz
3 g