Controller functions
Page 58
RES-430
Version 1
The timing sequence can be represented as follows:
Required controller settings:
The following controller settings are required for time control (the basic settings such as the temperature range,
alloy etc. should already have been entered).
The settings should be undertaken in the specified order.
Then:
Step in Configuration
menu
Setting
210 (Cooling mode)
"Absolute"
211 (Start of heatsealing
time)
"When temperature
reached"
212 (Relay K1 function)
"When start signal
present"
Step in Settings menu
Setting
101 (Heatsealing tempera-
ture)
180°C
103 (Starting delay)
0.0 s
ACTUAL temp.
START signal
180°C
t
t
OFF
0
80°C
1s
t
Open
Relay K1
Closed
95% of 180°C
ON
FOOT SWITCH
OFF
ON
signal
t