Controller functions
Version 1
RES-430
Page 49
The "START" signal is activated by means of a control contact at terminals 12+14.
The "START" signal is disabled as long as the "AUTOCAL" function is executing in the Settings
menu (with step 107).
The set point that is selected for the heatsealing temperature (step 101 in the Settings menu) must be greater than
40°C. If not, the heatsealing band will not be heated up.
As of software revision 008, it is not possible to activate the "START" signal again (in other words,
relay K1 or the solenoid drive cannot be energized) for 200ms after it is deactivated in order to pre-
vent bouncing or oscillation of the driven closing movement.
10.12 Cycle counter
Each activation of the "START" signal during operation is detected by a cycle counter integrated in the controller.
Actuations of the "HAND" key are not counted. The counter reading can be displayed with step 214 in the Config-
uration menu.
The cycle counter is reset to 0 if the "ENTER" key is pressed or if the maximum count of 999.999.999 cycles is
exceeded.
10.13 Single/double sealing
Step 240 determines how the two heatsealing bands are heated, depending on the design of the machine or
equipment.
If two heatsealing bands for top and bottom heating are installed in the machine, one of these bands can be deac-
tivated for specific applications.
The required settings can be configured with step 240:
1.
"Double" (Factory setting)
The two heatsealing bands are heated simultaneously. The temperature of both bands is controlled together.
2.
"Single"
If two heatsealing bands are connected to the controller, only the first is heated. The second band is not used.
Only the temperature of the first heatsealing band is controlled.
If only one heatsealing band is connected to the controller, you must set "Double" with step 240.
The controller will otherwise be overloaded and damaged beyond repair.
If you change the configuration with step 240, you must run the AUTOCAL function with step 107. If
not, the controller will no longer function correctly.
RES-430
14
START
(HEAT)
with
contact
0V
12
max.
5mA
!
!
!
!