Startup and operation
Page 30
RES-430
Version 1
Software revision 007:
The temperature diagnosis function is always active. The diagnosis begins if the ACTUAL temperature exceeds
the lower tolerance limit and simultaneously corresponds to 95% of the SET temperature. The diagnosis ends at
the end of the parameterized heatsealing phase.
As of software revision 008:
The temperature diagnosis function can be activated and deactivated with step 217 in the Configuration menu.
The following settings are possible:
1.
"OFF" (Factory setting)
Temperature diagnosis deactivated
2.
"ON"
Temperature diagnosis activated
If the temperature diagnosis is not activated byl the end of the configured sealing time (i.e. if the ACTUAL temper-
ature does not exceed the upper or lower tolerance band limit), the corresponding error code (309, 310) is indi-
cated.
If the temperature diagnosis function is activated, an additional delay time between 0 and 9.9s can be parameter-
ized for temperature monitoring with step 218 in the Configuration menu. This delay time starts when the ACTUAL
temperature reaches 95% of the SET temperature. The temperature diagnosis function is activated as soon as
the delay time elapses (in the case of software revision 008, the ACTUAL temperature must also have exceeded
the lower limit of the tolerance band in order for the diagnosis function to be activated).