Startup and operation
Page 24
RES-430
Version 1
The current condition of relay K1 (or the optional solenoid drive) is indicated by means of a separate icon. If the
icon is visible, the normally open contact of the relay is closed or the solenoid drive is active.
Separate settings can be entered for the individual timeouts. These settings are possible with steps 103, 104 and
105 in the Settings menu and with steps 210, 211 and 212 in the Configuration menu.
The options available with these advanced settings are described below.
9.3.2
Setting the starting delay
The start of the heating process can be explicitly delayed by entering a starting delay time with step 103 in the
Settings menu, e.g. in order to bridge the closing time of the heatsealing bars.
When the "START" signal is activated, the controller waits for the time specified with this menu step to elapse
before commencing the heating process.
The starting delay can be set in the range from 0 to 9.9s. A delay of 0s is defined as the factory setting. In this
case, the heating process begins as soon as the "START" signal is activated.
ACTUAL
temp.
START
signal
ON
T
t
t
0
0
t
1
t
1
= Starting delay