Page 32
System configuration
© 2017 Ropam Elektronik
Tab: Outputs - Notifications.
The tab allows you to configure notifications when the modules output state changes. The window and
its configuration is analogous to the notification option from inputs.
Logical state '0' = output inactive:
- polarity 'NO'
O2-O4 = hiZ (high impedance)
- polaritz 'NC'
O2-O4 = GND (ground)
Logical state '1' = active output
- polarity 'NO'
O2-O4 = GND (ground)
- polaritz 'NC'
O2-O4 = hiZ (high impedance)
Information:
OUT1-OUT4:
list of outputs to which the settings apply.
SMS 0-> 1:
column to enter the text of the SMS sent when the output change to the state '1' active.
SMS 1-> 0:
column to enter the text of the SMS sent when the output change to state '0' is inactive.
CALL 0-> 1:
column to activate a voice call (CLIP or voice message) when you change the output
state to '1' active.
E-mail to:
column to mark the recipient's number from the list to send when changing the output to
status '1' active.
VSR 0-> 1:
column to enter the message numbers played during a voice call from the VSR-2
synthesizer or from the unit's memory when the output is changed to '1' active.
CALL 1 -> 0:
Voice call activation column (CLIP or voice message) when switching to a '0' state
inactive.
VSR 1-> 0:
column to enter the message numbers played during a voice call from the VSR-2
synthesizer or from the unit's memory when the output is changed to '0' inactive.
Tel / Email:
Columns to mark recipients of SMS / CALL / E-MAIL messages.
- no SMS content = no SMS transmission at the given event.