Programming and Parameters
3-13
Motor Control File
(File B)
F
ile
B
Gr
oup
No.
Parameter Name and Description
See
Values
Relate
d
MO
TO
R CONTR
O
L (File B)
Mo
to
r Da
ta
040
[Motor Type]
Set to match the type of motor connected.
Default:
Options:
0
0
1
2
“Induction”
“Induction”
“Synchr Reluc”
“Synchr PM”
041
[Motor NP Volts]
Set to the motor nameplate rated volts.
Default:
Min/Max:
Units:
Drive Rating Based
0.0/[Rated Volts]
0.1 VAC
042
[Motor NP FLA]
Set to the motor nameplate rated full load
amps.
Default:
Min/Max:
Units:
Drive Rating Based
0.0/[Rated Amps]
×
2
0.1 Amps
043
[Motor NP Hertz]
Set to the motor nameplate rated
frequency.
Default:
Min/Max:
Units:
Drive Rating Based
5.0/400.0 Hz
5.0/500.0 Hz
0.1 Hz
044
[Motor NP RPM]
Set to the motor nameplate rated RPM.
Default:
Min/Max:
Units:
Drive Rating Based
60/30000 RPM
1 RPM
045
[Motor NP Power]
Set to the motor nameplate rated power.
(1)
See
Default:
Min/Max:
Units:
Drive Rating Based
0.00/100.00
0.00/412.48
0.01 kW/HP
(1)
046
[Mtr NP Pwr Units]
Selects the motor power units to be used.
Default:
Options:
0
1
Drive Rating Based
“Horsepower”
“kiloWatts”
047
[Motor OL Hertz]
Selects the output frequency below which
the motor operating current is derated.
The motor thermal overload will generate
a fault at lower levels of current.
Default:
Min/Max:
Units:
Motor NP Hz/3
0.0/500.0 Hz
0.1 Hz
048
[Motor OL Factor]
Sets operating level for motor overload.
Motor FLA x OL Factor = Operating Level
Default:
Min/Max:
Units:
1.00
0.20/2.00
0.01
049
[Motor Poles]
Defines the number of poles in the motor.
Default:
Min/Max:
Units:
4
2/40
2 Pole
E C
32
E C
E C
Summary of Contents for PowerFlex 70
Page 4: ...soc 2 Notes ...
Page 134: ...A 18 Supplemental Drive Information Notes ...
Page 168: ...Index 14 ...
Page 169: ......