Installation/Wiring
1-23
Table 1.L PowerFlex 70 EN61800-3 First Environment Restricted Distribution
Fr
am
e
Drive Description
First Environment Restricted Distribution
Restrict
Motor Cable
to:
Internal
Filter Option
External
Filter
(1)
Comm Cable
Ferrite
(2)
Common
Mode Core
(3)
A Drive Only
40 m (131 ft.) –
✔
–
–
Drive with any Comm Option 40 m (131 ft.) –
✔
–
–
Drive with Remote I/O
40 m (131 ft.) –
✔
✔
–
B Drive Only
12 m (40 ft.)
✔
–
–
–
Drive with any Comm Option 12 m (40 ft.)
✔
–
–
–
Drive with Remote I/O
12 m (40 ft.)
✔
–
✔
–
C Drive Only
12 m (40 ft.) –
–
–
✔
Drive with any Comm Option 12 m (40 ft.) –
–
–
✔
Drive with Remote I/O
12 m (40 ft.) –
–
✔
✔
D Drive Only
12 m (40 ft.) –
–
–
–
Drive with any Comm Option 12 m (40 ft.) –
–
–
–
Drive with Remote I/O
12 m (40 ft.) –
–
✔
–
E Drive Only
30 m (98 ft.) –
✔
–
–
Drive with any Comm Option 30 m (98 ft.) –
✔
–
–
Drive with Remote I/O
30 m (98 ft.) –
✔
✔
–
(1)
External filters for First Environment installations and increasing motor cable lengths in Second
Environment installations are available. Roxburgh models KMFA (RF3 for UL installations) and MIF
or Schaffner FN3258 and FN258 models are recommended. Refer to
and
(USA) or
respectively.
(2)
Two turns of the blue comm option cable through a Ferrite Core (Frames A, B, C Fair-Rite
#2643102002, Frame D Fair-Rite #2643251002 or equivalent).
(3)
Refer to the 1321 Reactor and Isolation Transformer Technical Data publication, 1321-TD001x for
1321-Mxxx selection information.
Summary of Contents for PowerFlex 70
Page 4: ...soc 2 Notes ...
Page 134: ...A 18 Supplemental Drive Information Notes ...
Page 168: ...Index 14 ...
Page 169: ......