3-58
Programming and Parameters
Selected Option Definitions – [Analog Outx Sel], [Digital Inx Sel],
[Digital Outx Sel]
INPUTS & OUTPUTS (File J)
Di
gi
tal
Outp
ut
s
383
387
[Dig Out1 OffTime]
[Dig Out2 OffTime]
Sets the “OFF Delay” time for the digital
outputs. This is the time between the
disappearance of a condition and
de-activation of the relay.
Default:
Min/Max:
Units:
0.0 Secs
0.0 Secs
0.0/600.0 Secs
0.1 Secs
Fi
le J
Gr
oup
No.
Parameter Name and Description
See
page 3-2
for symbol descriptions
Values
Relate
d
Option
Description
Related
At Speed
Relay changes state when drive has reached commanded speed.
Excl Link
Links digital input to a digital output if the output is set to “Input 1-6 Link.”
Input 1-6 Link
When Digital Output 1 is set to of these (i.e. Input 3 Link) in conjunction with Digital Input
3 set to “Excl Link,” the Digital Input 3 state (on/off) is echoed in the Digital Output 1.
Manual Mode
Either the HIM or I/O Terminal Block (analog input) has control of the speed reference.
MOP Dec
Decrements speed reference as long as input is closed.
MOP Inc
Increments speed reference as long as input is closed.
MtrTrqCurRef
Torque producing current reference.
Param Cntl
Parameter controlled analog output allows PLC to control analog outputs through data
links. Set in [AnlgX Out Setpt], parameters 377-378.
Param Cntl
Parameter controlled digital output allows PLC to control digital outputs through data
links. Set in [Dig Out Setpt], parameter 379.
PI Reference
Reference for PI block (see
Process PI for Standard Control on page C-11
).
Precharge En
Forces drive into precharge state. Typically controlled by auxiliary contact on the
disconnect at the DC input to the drive.
Run Level
Provides a run level input. They do not require a transition for enable or fault, but a
transition is still required for a stop.
RunFwd Level
RunRev Level
Run w/Comm
Allows the comms start bit to operate like a run with the run input on the terminal block.
Ownership rules apply.
SpdFdBk NoFilt Provides an unfiltered value to an analog output. The filtered version “Speed Fdbk”
includes a 125 ms filter.
Sync Enable
The fiber feature Synchronized Speed Change has been enabled. Allows a coordinated
change in drive speeds to change machine speed.
Torque Est
Calculated percentage of rated motor torque.
Traverse Enable The Traverse function has been enabled. This adds a triangle wave and square wave
modulation to the speed reference.
Summary of Contents for PowerFlex 70
Page 4: ...soc 2 Notes ...
Page 134: ...A 18 Supplemental Drive Information Notes ...
Page 168: ...Index 14 ...