4-11
Programming Reference
For a detailed description of:
Second Menu General parameters
Second Menu Vector parameters
Second Menu Volts/Hertz parameters
Second Menu RMI parameters
Refer to:
Section 4.6.2
Section 4.6.3
Section 4.6.4
RMI instruction manual D2-3341
4.6
Second Menu Parameters
The Second Menu contains parameters used for more complex applications. Within
the Second Menu are General (P.---) parameters that apply to both vector and V/Hz
programming and Vector (U.---) or Volts/Hertz (H.---) parameters. If an optional RMI
board is installed in the drive, RMI (r.---) parameters are also contained in the
Second Menu.
Access to the Second Menu parameters is enabled/disabled using the Second
Menu Password parameter (P.006). Refer to section 4.6.1 for more information.
4.6.1 Entering the Second Menu Password
ATTENTION: It is the user's responsibility to determine how to distribute
the second menu password. Reliance Electric is not responsible for
unauthorized access violations within the user's organization. Failure
to observe this precaution could result in bodily injury.
The Second Menu Password parameter (P.006) is used to enable/disable access to
the Second Menu parameters. When access is disabled, the Second Menu
parameters cannot be displayed or changed (refer to figure 4.1). To enable access,
a factory-set password is entered into P.006. Access to the Second Menu
parameters will then remain enabled until the password is entered into P.006 again.
!
Step 1. Press the PROGRAM key until the PROGRAM LED turns on to enter
program mode.
If P.--- is not displayed, press the
£
key or
the
¥
key until it is.
AUTO
MAN
Forward
Reverse
PROGRAM
RUN
JOG
STOP
RESET
START
ENTER
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM