4-53
Programming Reference
P.066 to P.069 Network Output Register 1 Source through
Network Output Register 4 Source
These parameters
select the signal
written to the option
port network output
registers 1 through 4.
See figure 4.9.
Parameter Range:
0 = (P.066) Motor Kw display value
(P.067) Motor torque display value
(P.068) Output power factor
(P.069) Encoder counter (x4)
1 = Speed reference rate limit output*
2 = Speed reference at the ref/fdbk summing
junction (includes OCL output and current
compounding)*
3 = Speed loop feedback*
4 = Speed loop error*
5 = Speed PI output*
6 = Outer control loop feedback*
7 = Outer control loop error*
8 = Outer control loop output*
9 = Terminal strip analog input normalized to
speed (see Appendix F)
10 = Terminal strip analog input scaled (see
Appendix F)
11 = Torque reference*
12 = Torque feedback*
Default Setting:
0
Parameter Type:
Tunable
Refer also to parameters: N/A
*These signals are valid only in vector control (P.048 = UEC).
Refer to the AutoMax Network Communication Option Board instruction manual
(D2-3308) for the AutoMax network register map.
Refer to the ControlNet Network Communication Option Board instruction manual
(D2-3390) for the ControlNet network register map.