![Rockwell Automation Allen-Bradley PowerFlex 7000 User Manual Download Page 326](http://html1.mh-extra.com/html/rockwell-automation/allen-bradley-powerflex-7000/allen-bradley-powerflex-7000_user-manual_1475431326.webp)
326
Rockwell Automation Publication 7000L-UM301F-EN-P - March 2020
Chapter 5
Component Definition and Maintenance
Replacement Procedure
1.
Ensure control power has been isolated and locked out.
2.
Disconnect the terminals at the unit.
3.
Remove the two M6 bolts per
.
4.
Extract the power supply complete with bracket from the drive.
5.
Remove the bracket from the failed power supply (four M4 screws and
nylon shoulder washers).
6.
Attach bracket to replacement power supply.
7.
Repeat Steps 5, 4, 3, 2 and 1 in this order to replace the unit (see
8.
Reapply control power and verify voltage levels.
Figure 273 - Replacement of AC/DC Power Supply on Low Voltage Panel
TIP
Make sure the Black Insulation is between the AC/DC power supply and
the mounting plate.
Power Transformer
Hold-up Capacitors
Fuse Blocks
Power Supplies
(Optional)
AC/DC
Power Supply